Romex In Bx Armored Cable

QUESTION:  can I run (2) 14-2 romex wires in (1) 3/4 BX Armored cable?



SETUP: I am finishing my basement and a few main floor circuits are intermingled with the basement lights and outlets.  In finishing the basement, all basement electrical will be on its own circuit. Therefore, I need to rewire some main floor items.



For instance, the main floor living room outlets go through the den area below in the basement. The 3/4 BX cable goes through the ceiling to the outlets.



PLAN:  I plan to cut the armored cable shortly after it comes out of the ceiling (main floor floor) and just connect the first floor outlets in a series using the proper bushing and BX cable ends. I will strap the BX cable ends down and the romex as soon as it comes out.



The electrical inspector already gave me thumbs up on doing this for the electric oven and cooktop (bigger wires of course).



I searched and couldn't find anything to this specific question.



Any input?



B
      


Similar Tutorials

How to Lay Sod - The Right Way!
   - Make sure the green side faces up! And, there are a few more steps if you want to ensure a nice looking lawn. Prepa ...
The Difference Between Volts, Amps, and Watts
   - This article explains the difference between Volts, Amps, and Watts in an easy-to-understand non-scientific way. T ...
Water is Leaking from the Toilet – What do I do? (How to replace the wax seal for a toilet.)
   - If there is water leaking from the toilet, you need to make sure that you know from where the water is leaking. Che ...


Similar Topics From Forums

I've been the owner of a 1930s era Colonial Revival that our first major project is to rewire the house. We have a 100A main box that is maxed out, a combination of cloth 2-wire, flex, and some cracking Romex along with some downright dangerous open wiring in the basement, tapped wiring in the kitchen and study, some gangboxes that were wallpapered over in the bedrooms that we assume were wall lights (we have similar wall lights in the bathrooms), inadequate outlets in most rooms, no GFI. Etc. Etc. In addition the bathrooms are small and lack wall switches or outlets (they have two pull-cord wall lamps, with one lamp with a outlet.



Here is a floor plan with electrical represented on the ground and second floor. Still working on mapping the basement and the attic (which has a 3/4 converted finished "bonus" room.



My Father-In-Law who is a licensed electrician has promised to gracefully donate a couple months of his time to rewire everything. Also a bonus in this is the majority of outlets are mounted on the baseboard trim and not in the plaster.



My plans are to go with a single 200A main, likely double the amount of outlets in each room, GFI where needed.



While I know some basics, I want to familiarize myself a bit more on what is the best approach to rewire. For instance should I look at running conduit in just one spot of the house, or should I run two on each end of the house? I plan to do some major remodeling of some rooms in the future, especially the kitchen and bath so what are the best ways to ensure I have an easier time with these remodels?
      
I have a 50 foot hdmi cable that is hooked to my TV, run through my wall to my basement then over and upto a closet where the cable is hooked to my surround sound. Unfortunately my basement ceiling is finished in drywall and there is no access to replace the cord. To make a long story short a cable TV provider came to my house to change out a box and broke the prongs on the hdmi cable. My question is, can HDMI ends be spliced or replaced somehow without replacing the whole cable.
      
I want to run Romex from a j-box, that is in the ceiling of my basement, to the main panel.  I know that I can run Romex from the box along the face of the joist (not the bottom), but what are my options once the Romex gets to the wall?  The joist I am using, conveniently enough, meets the wall ideally for where the panel is.  However, I've read that I need to run the Romex through EMT, or some form of conduit.



If you look at the picture I've attached, the panel is mounted on a piece of plywood that extends out underneath the joist.  Can I just staple the Romex to the plywood and then run it into the panel without using any conduit?  The cast iron pipe makes using any conduit quite a problem.



The cable you see is MC Lite, but I want to replace it with Romex.  There are going to be up to 9 more lines coming into the panel this very way.
      
I'm currently working on a house built in the 1930's. The electrical is a mess with a combination of a switch panel  and a fuse box with most of it still being knob and tube. I'm running a new electrical line to the air handler in the basement. This is due to it currently being tapped off a light circuit which also feeds an outlet in the kitchen, a bedroom, and half the outlets upstairs. (There's no rhyme or reason to the current electrical setup). 



  My main question is I'm running  12NM through bored holes in the studs to the air handler. Once I get to the handler and run it down to where it enters the appliance and switch box will I run in to codes problems. Should this run in the basement be inside a conduit or is NM cable okay? 

  Any guidance would be appreciated. 
      
Okay, I am fairly new to wiring but its not the wiring I am wondering about.  It is running the wires.  I have 2 rooms in my house, 2 story and an attic, on the main floor that doesn't have any overhead lighting, only can use floor or table lamps right now.  The ceilings are about 10 feet tall.  There are outlets in the room so I do have power I can tap into for the lighting, but how do I go about running the wires up into the ceiling?  I do know I have to cut the hole for the lighting but will i have to put cut flaps in the drywall where ever there is a brace to drill holes to run the wires.  I am going to go from the middle of the ceiling straight back to the wall and then down to the switch that I will put in and then down to the outlet to tap into for the power.  I am just trying to do this the easiest way to minimize any drywall repair that will be needed.  Any help or suggestions from anyone is greatly appreciated and if you have questions please ask and I willl try to answer them.
      
So we just bought a circal-1930s house, and one very large project looming is redoing the eletrical. The house has a mix of BX, cotton-wraped romex, and some very cracked romex running around the house. combine that with some very odd additions for outlets, bad light switch placement, it's just going to be a large project.



My father in law, a licensed electrician, has promised to do the rewiring of the house this summer. The problem is I plan to do some major renovations in the coming years (namely the kitchen).



I am already drawing up floor plans now so I can stategically think of where to put needed outlets, but should they be installed at this time? Is it worth the headache to install new outlets now and put them in their proper locations when the reno comes?
      
I recently switched over from AT&T phone/cable/Internet service to Cablevision. 



The problem with both services is the coax cable coming through a hole in the wall from outside and then a phone line from their modem stapled to the floor board and tied into the phone outlet inside.  Then there's my phone lines, the coax cable to the TV... It's a disgusting mess.



I'd like to install a combination phone line and cable outlet in the wall and get rid of as much loose wiring as possible.  The phone line would come through the same area as the cable and I'd wire it on the other end to the main box outside the house.



I have no experience with this so my question is can I take the phone line from the Cablevision modem and simply plug it into the outlet and get all the phones in the house to work or does it have to be hard wired or piggybacked inside the outlet?
      
Hey all, new to the forum and had a few questions about the electric I plan on installing in my basement I am working on finishing.   Here is what the plans call for...



- Bathroom

  - 2 Lights, one GFCI, vent fan

- Home theater

  - Projector, Sound system, various other electronics

- General Lighting throughout

  - 14 Recessed lights approx 60 watt bulbs

  - 14 outlets

  - Mini bar fridge

I will have to run the line from the garage to the basement and my question is should I go 15 or 20 and will I need more than one line to support this?  Any info or direction you guys can give would be greatly appreciated!!



Tom
      
hi everyone.



i am installing 4" recessed lighting throughout my main floor.  my house was built in the 40's and the previous owner installed drywall over the existing lath and plaster ceiling.  so I've cut a trench down the center of my room to drill floor joists to run wiring and cut my holes for the new lights.

the lights are fire rated and do not require insulated cans for a traditional installation in a drywall ceiling.



question i have is with the additional 1/2 to 3/4" of lath and plaster above the drywall, should these lights now have insulated cans or should i be fine with the cans I've got?  there is no insulation in ceiling.



any suggested would be appreciated.



thanks

d
      
Finishing basement and have a few questions...



1. Have already bought recessed cans. Commercial Electric brand. I have now read a few places that these are junk. Why exactly and should I return them? Need to know know before I paint them black.



2. I plan on installing 12 lights on new 15A circuit using 2 switches one for left side of basement one for right (6 x 6). This is OK yes? Both switches will be in same box. And will be only thing on this new circuit.



3. Assuming I am running hot lead from main panel to switch box...there is no fancy wiring that needs to be done correct? 14/2 black to black, white to white except at switch correct?