What Is The Best Way To Find Bootlegged Outlets
Today I was fixing the water valve to the washing machine, and to get access to the water line, I had to disassemble an outlet. To my shock (no pun intended), I discovered that some moron bootlegged the outlet by connecting neutral and ground together.
Now I'm concerned that I may have this elsewhere in the house. What is the best way to test for this? Obviously I will see 120 V from hot to ground in any case, so that doesn't work. Continuity between neutral and ground is normal, because they are connected at the main panel; I measured the resistance between neutral and ground at an outlet close to the main panel, and it was virtually zero. But that doesn't meat it's bootlegged. I don't really want to take each outlet apart. And even if I do that, how would I know that the moron didn't connect ground to neutral somewhere inside a wall? Thanks, Similar Tutorials
How to Lay Sod - The Right Way!
- Make sure the green side faces up! And, there are a few more steps if you want to ensure a nice looking lawn. Prepa ...
The Difference Between Volts, Amps, and Watts
- This article explains the difference between Volts, Amps, and Watts in an easy-to-understand non-scientific way. T ...
Water is Leaking from the Toilet – What do I do? (How to replace the wax seal for a toilet.)
- If there is water leaking from the toilet, you need to make sure that you know from where the water is leaking. Che ... Similar Topics From Forums
this topic came up on another thread but its buried pretty deep. it is my understanding from several experienced posters that under normal circumstances all neutral current should flow back to the utility neutral, not the grounded plumbing or rods.
i am trying to figure out why. bear with this simplistic example. 100a service - 3 wires in - A (hot+), B (hot-) and N (neutral). circuit 1 on A is using 12 amps circuit 2 on B is using 7 amps so a total of 5 neutral current amps have to go somewhere. they could all flow back on N, but if bonded to N at the panel is a low resistence connection to say, copper water pipes, wouldnt some of the current flow there? is the utility neutral supposed to be so low resistence that none of the current would flow to the grounds? if that is the case i need to call my utility ASAP because a considerable amount of current flows to my main ground. where i am struggling is i dont see how a utility pole or transformer would be any lower resistance than miles of metal plumbing and since they are bonded together, the current can choose (i know wrong word but im not an electrican or an engineer) either path
i will have one of those fridges that have water supply for drinking water filtration and ice and the valve for that will be real close to the power outlet. my question is, does the outlet then need to be GFCI considering that it is that close but still it will never be wet because of the hose connecting it is sealed closed ?
Tearing out a wall cabinet uncovered a hole in the wall which I think I can install an outlet on. The problem is that the ground wires are to short to pull out far enough to attach to the outlet.
However, the box in the wall is metal, so there should still be an path to the ground from the outlet right? Or is there something special about the green screw on the outlet which makes that the only safe spot to attach the ground to? box I uncovered: https://lh3.googleusercontent.com/-v...s538/photo.jpg fuzzy picture of the inside of the box showing the ground being attached to metal box: https://lh6.googleusercontent.com/-B...303_154810.jpg The outlet I want to install... (although I dont know how to pick the right outlet based on the limited info on the wiring I have, so any help with that would also be appreciated): http://www.homedepot.com/Electrical-...&storeId=10051
wanted to get feeback on my crude wiring diagram i put together for my small bathroom remodel. does it appear to be sound or am i way off base??
details: * 20A dedicated circuit * 12/2 wiring * outlet's will be GFCI * double gang box will contain: * timer unit for exhaust fan * double switch for heat lamp and lights * Ground wiring is not shown but each fixture/outlet/switch will be connected to ground wire * by calculations, the 34cu box is fine for the number of conductors/size of wiring. per box specs could handle 15/12g wires. * the scanner cut off the bottom part of the picture, the 2 lights on the right are fed from the same switch, neutral's connected together. F = Exhaust Fan L = Light HL = Heat Lamp T = Timer switch S = Switch H = Hot N = Neutral Wire Nuts are in the box connecting the pigtails Thank you for your input.
I have 3 wire direct bury feeder cable from a 200 amp meter base/sub panel to a 125 amp sub panel on a post 150' away and the 125 amp sub panel will feed a 30 amp RV outlet box.
The 3 wire feed was already there and I know it is not to 2008 code, but my question is: do I need to bond the neutral bar to the ground bar and to a ground rod at the 125 amp subpanel?
I have an outdoor light fixture that I am trying to replace. The house was built ten years ago.
When I removed the original lamp, I noticed one of the two leads was wired to the ground, and one was wired to the black wire, which is hot per my current sensor. There are three wires in the box - black, ground (bare copper), and white or neutral, all from a single romex cable. Unfortunately, I do not recall where the white was when I removed the original. I wired the new lamp per the instructions, something I have done many times before - black to black, white to white, and bare copper ground to ground. Nothing. The lamp and bulbs are brand new, and I have tried four separate bulbs. I checked the black and neutral with my current sensor and with the switch on and the lamp installed this way, both show as hot. With the lamp not installed, the switch on, and the wires disconnected only the black shows as hot. The switch is single pole, and appears to be wired correctly with a black to each screw on one side and a copper ground on the other. Assuming the new fixture was bad, I reinstalled the old fixture correctly - black to black, white to white, and bare copper ground to ground. Still nothing. No light, and I confirmed the bulb is good by putting it in another lamp. The only way to get it to light is to connect the neutral in the lamp to the bare copper ground. I capped the wires, turned the circuit back on, and identified all the outlets, switches and fixtures on the same circuit. I opened every one of them up (four lights and eight outlets) and found three (one switch and two fixtures in another room) where multiple commons connect. All were properly connected. My outlet tester shows all outlets as "correct". I found no instances of grounds connected to commons or vice-versa. Any ideas? Is it proper to wire this thing the way I found it? Thanks for any and all advice!
I have an older QO-Square D eight circuit panel. It is being used as a subpanel and when installed was not bonded.
The neutral bar consists of a bar mounted with one screw and a second bar mounted to it by standoffs. This second bar is where the bonding screw is. I can see no way to separate these two bars for proper bonding. There is no provision for mounting this second bar. I wish I could post a picture but I will have to work on that. I am thinking I will have to purchase a new panel but can't understand why neutral and ground cannot be separated.
Hello,
I currently have one light switch which operates an outlet in one of my bedrooms. I want to add a ceiling fan that has independent switches for the fan and light - but I want to make sure i'm wiring it correctly and safely. Current (First Pic)- Live hot feeds into bottom of switch (bottom insert hole) and the all of the bedroom outlets (pig-tailed) tie into the bottom of the switch on the screw. Coming out of the top of the switch is one hot which feeds to a single outlet. All of the neutral and grounds are tied together. New Plan (Second Pic)- Remove the constant outlet hot from the screw, add a new hot wire to the top of new switch and run a wire up to the attic for fan. Add another hot wire from the bottom of that switch to the third switch and run another wire up to the attic for the lights. Re-connect the constant outlet wire to the screw of the last switch. Connect all the neutrals and all of the grounds together. At the top of the ceiling, connect the neutrals and grounds together with the fans neutral and ground. Connect the fan hot to the fan switch hot, and the fan light hot to the light switch hot.
I'm trying to figure out how exactly this should be redone... right now there is a NM cable going from the panel though the rim joist and outside straight down into the ground and out about 2 ft into the sump well then it jus dangles there with a female plug end connected to that which the sump pump then plugs into... well this actually shorted out the other night and created a wonderful noise and sparks...
how should I redo this? right now its not even GFIC... just straight into a 20 amp breaker... I was thinking put an outside receptical on the side of the house run that straight thorugh the back of it into the rim joist and to the panel... have the outlet on that a GFIC outlet then run a underground line from that to the pump using UF cable with a similar female plug end inside the well (the well is about 11 ft deep and the plug is about 1 ft from the top right now... then that would just plug into the GFIC outlet on the side of the house... that outlet would of course have one of those clear enclosures around it that is water tight... suggestions? comments? code violations?
Hello all,
I recently installed an old elevator winch onto my pier to use as a boat lift. It's wired as 220v and it only draws 6 amps under full load. There are 3 wires supplying the winch, two hot wires and a ground / neutral. As you can probably tell, I'm not an electrician... Well, I finished wiring it all up and tested it out. It worked great. When it got dark, I started pulling my aluminum ladder out of the water and I noticed that the cable coming off of the winch was lightly arcing on the ladder as they touched. I unplugged the winch and the arcing went away. Something is obviously wrong and needs to be fixed. I can touch the winch and cable without feeling any electrical shock, but I'm standing on a wooden pier deck. I guess since the ladder was still partly in the water, it was acting as a ground. What can I do to stop this? Can I add a ground rod? Will this ground rod have to be on land? Will a ground rod even solve the problem, or is it more like a band-aid? Can anyone tell me what's causing the problem? I'd like to swim in the water, but I'd prefer to stay alive... If you guys need any more info to help me out, I'll be as quick as possible. I'd like to get this boat lift safe before I use it or swim. Thanks, Patrick |