Receptacle And Water Faucet

if a 110v receptacle is located near a water faucet on the inside of a building, does it need to be GFCI protected? no sink involved.
      


Similar Tutorials

How to Lay Sod - The Right Way!
   - Make sure the green side faces up! And, there are a few more steps if you want to ensure a nice looking lawn. Prepa ...
The Difference Between Volts, Amps, and Watts
   - This article explains the difference between Volts, Amps, and Watts in an easy-to-understand non-scientific way. T ...
Water is Leaking from the Toilet – What do I do? (How to replace the wax seal for a toilet.)
   - If there is water leaking from the toilet, you need to make sure that you know from where the water is leaking. Che ...


Similar Topics From Forums

Hi all,



I have read a few posts here about others having problems with receiving a shock while touching the faucet or water from the faucet in certain rooms. Today I experienced this problem in my kitchen. I was able to narrow the problem down to one breaker on my box, specifically one set of outlets. My question is can a faulty outlet cause this to happen?



I currently have the breaker in question flipped off until I can replace the outlet and see if that fixes the problem. There haven't been any changes to the electrical or plumbing in quite a while. This happened completely out of the blue.



Any advise that you might have would be greatly appreciated.



Jess
      
Can an outside receptacle be protected by a GFCI on the inside of my garage or must the recep. outside be a GFCI aslo?
      
Hello,  what could be the cause of the kitchen sink faucet stream feeling a slight tingling sensation when the garbage disposal is running?

Can't be good, I know!

Possibly a grounding issue?  200 Amp service w/ two subpanels.

House is about 25 years old.

Thanks for any help how to start troubleshooting.
      
I am new to the forum so kindly bear with me.  I live in Mesa, AZ and have just had a PEX repipe done to bypass my copper hot water lines.  (God don't ask!  A real problem here with slab foundations.  I already had my kitchen jack hammered once.  It is NOT pretty!).

It seems really odd to me that just because it is a dedicated circuit  that code would not require that circuit to be GFCI protected.

I have a dedicated 20 amp duplex 12 AWG wire outlet under the sink and it is within a few inches of the water lines.  The outlet serves a switch for the garbage disposal and serves my dishwasher which is always hot. 

  Now that I have all my maple cabinets pulled out I thought I might change the outlet to a GFCI just to be safe.  I have a ground wire, a red wire, a black wire and a white wire.  As it is dedicated I think I should use the LINE sided instead of the LOAD side but I am not sure where the wires should go.

Could someone give me info on this?  It would be greatly appreciated.  Thank you.
      
That means it applies to the entire country

Permits & Inspections are usually required for ALL electric work

It may not be legal for you to do your own work, Check with your local Building Dept

This thread will be added onto as a form of "Cliff Notes" for the NEC

If there is something that needs to be corrected, or if you wish to add to this thread; please let us know



The NEC is available online, you may have to sign up for an account to view it:

http://nfpaweb3.gvpi.net/rrserver/br...NFPASTD/7008SB

(may not be working)



Draft Version:

http://www.nfpa.org/assets/files/PDF...08ROPDraft.pdf 



Also a link to State specific NEC/Building codes:

http://bulk.resource.org/codes.gov/



New Code book comes out every 3 years, it is not always fully accepted by States & sometimes not until 1-2 years later

Local codes can vary from the NEC



210.23 An individual branch circuit shall be permitted to supply any load for which it is rated (some think you can only load to 80%)



210.50 Required Branch circuits

14g wire is rated for 15a, 12g wire is rated for 20a

15a outlets ONLY on a 15a circuit

15a/20a are allowed on a 20a circuit

A single 15a receptacle is not allowed on a 20a circuit

AFCI protection is required almost every where under NEC 2008

Exceptions are GFCI required: bathrooms, kitchens, laundry (GFCI if sink within 6' of receptacle), garage & outside circuits



Bathroom requires a dedicated 20a GFCI protected circuit that can serve outlets in multiple bathrooms

OR

Outlets & Lights in One bathroom



Kitchen requires 2 dedicated 20a GFCI protected circuits for counter (no lights)



Laundry area requires a dedicated 20a GFCI protected circuit

.

.
      
Hello,

We're installing a steam shower unit & need to run new electrical wiring.  We have a few questions & hope someone can help!



We have three power cords (water pump, heat pump, steam generator) & none of them currently have plugs.  The specs are as follows:  3000W steam generator 110v - 30 amp GFCI breaker, 12 v lighting, 1.2 hp water pump 110 v - 30 amp GFCI breaker, & a 1500W heat pump 110v 12.5 amps.  It says you can run the heat pump off the same circuit as the rest of the unit.



Ok, so.. we're wondering what the easiest & cheapest way of going about this is.  We want it to be SAFE first & foremost, but also want to keep expense at a minimum.



Thank you for any advice you have!




      
i will have one of those fridges that have water supply for drinking water filtration and ice and the valve for that will be real close to the power outlet.  my question is, does the outlet then need to be GFCI considering that it is that close but still it will never be wet because of the hose connecting it is sealed closed ?
      
Is there any limitation as to how many receptacles can be protected by one GFCI receptacle?  For example, can I start the circuit with a GFCI and have another 8 receptacles downstream from it?
      
Hi all, this is my first post, so...my kitchen was just renovated and the electrical outlets are on the walls and I wanted them in plugmold under the cabinet. Why didn't it happen?  Long story, but I'm doing it myself now.  The electrical receptacles are on 2 separate circuits with a gfci receptacle on each and neither circuit has a receptacle outside the kitchen where I can put the gfci's, so I'm putting gfci breakers in the panel instead. I've run into a different problem on each circuit that'd like some advice on.



Circuit 1: this is a 20 amp circuit.  I have to plug this circuit's neutral wire into the gfci breaker, but I couldn't see which neutral wire matched the hot wire (buried in mess of wires) and I don't have a continuity tester so I just pulled one neutral at a time (tedious) until the circuit failed, but it never failed. So I did this again for every neutral...same result. This circuit shares a few boxes with other circuits so I'm wondering if the neutrals on different circuits are tied together somewhere, and if so I'm pretty sure, but not completely, that that's not going to work with the gfci breaker.  So I didn't install that gfci breaker since I'm not confident it would actually gfci (yep i verbified gfci).  What do you think?



Circuit 2:  this is a 20 amp circuit.  This circuit currently has the refrigerator, gas stove and range hood, and then a gfci in front of 3 electrical receptacles, which already sounds bad since I thought the kitchen receptacles required 2 dedicated circuits. I replaced that breaker with no problem, but it tripped after a few minutes and continued to trip every few minutes. I haven't changed anything else on that circuit yet and it's never tripped before, but now it is, so I put the old breaker back for now. The current gfci receptacle is only protecting the 3 outlets since the appliances are ahead of it. I know you wouldn't normally want the appliances gfci protected, so do you think the refrigerator motor may be a problem?  Do I need the appliances on a separate circuit?  What would you suggest I do?



Thanks, and if you're wondering "why all the effort?", it's partly because I'm meddlesome, partly because I'm bored, and partly because the backsplash tile is to be on showcase, not the electrical receptacles.
      
Hello.



I recently purchased a home that has a a new grounded breaker panel but none of the outlets themselves are grounded save the hvac system in the basement. I had an electrician come and he said the fastest way to get it done is to switch the appropriate breakers to GFCI breakers in my service box and then I can change the outlets and then just put the stickers that say ungrounded etc on the new 3 prong receptacles. he called the inspector to double check and the inspector told him that he can't do it this way but he needs to find the first outlet in the loop from each breaker line and change that receptacle to a gfci and then we can change each receptacle to 3 prong in that loop.



Wouldn't just changing the breaker do the same thing? also if I did just install a Gfci receptacle on the first outlet in the loop, if it breaks wouldn't the rest of the outlets behind that gfci not function until I replaced the Gfci outlet where as a breaker would just pop and I can simply go turn it back on?



Just wanted to get some opinion from the experts as I'm willing to spend more on doing gfci breakers and am confused as to why the inspector suggested the way he did



Thanks for any help!