Wiring Ingersoll Rand Replacement Control Box

I have a 5 hp, guess it's a 80 gallon, 220 volt Ingersoll Rand compressor and had problems with the motor not wanting to start. I found a replacement box that included the Siemens starter and a new reset. The only thing this new box doesn't have is the two 5 amp fuses and didn't figure I needed to use them so I didn't add them to the new box.(?) After wiring the unit I have found the only way the compressor will kick on is if I hold down the Siemens starter re-set.



I know I have the motor wired properly and the wires from the pressure switch expect the white one. It originally went to one of the two fuses and than to where I currently is.(?)



The black motor wire was connected to the bottom of the reset (lower left), which is out of view in the pic

The white motor wire was connected to the bottom right of the Siemens starter

The motor ground was connected to the ground terminal on the box.



The pressure switch black wire was connected to the top right of the starter.

The pressure switch with wire was connected to the top left of the starter.

The ground was connected to the ground terminal on the box.



The incoming black hot wire was connected to the top left of of the starter.

The incoming white hot wire was connected to the top right of the starter.

The ground was connected to the ground terminal on the box.



Any idea what's wrong and have I included enough information?



Thanks, Shawn
      


Similar Tutorials

How to Lay Sod - The Right Way!
   - Make sure the green side faces up! And, there are a few more steps if you want to ensure a nice looking lawn. Prepa ...
The Difference Between Volts, Amps, and Watts
   - This article explains the difference between Volts, Amps, and Watts in an easy-to-understand non-scientific way. T ...
Water is Leaking from the Toilet – What do I do? (How to replace the wax seal for a toilet.)
   - If there is water leaking from the toilet, you need to make sure that you know from where the water is leaking. Che ...


Similar Topics From Forums

I have two 3-way switches in my master bath that have never worked properly. The house is very old and has been worked on over the years by many different people with greatly varying levels of skill. I was finally fed up with these switches and tried to fix them. I tried to follow instructions I found online, so with the power off I disconnected all the wires from both switches, then turned the power back on and used my volt-meter to discover which wire was hot. It turned out to the a red wire at switch #1. The other two wires are white and black (and yes, there also is a ground). I connected this hot wire to the darkest screw, connected the white and black to the other two screws and tried to test for continuity at the other switch. I couldn't get a reading on any of the wires at the other end. I tried turning the power back on and testing to see which wire was now hot at the second switch. It was the white wire, so I attached that to the darkest terminal, and attached the red and black to the other two terminals. The switches don't work any better than they did before I started - that is, both switches have to be turned on for the light to come on. What is my problem here? Thank you!
      
I bought a replacement motor (Dayton 6k778k) for my attic fan.  I removed the old one and it has two wires coming out that connect to two wires that go down to the light switch that turns it on.  They were connected by those plastic twist things.  So, I open up my new motor assuming that there would be two wires coming out of it that I would just connect to the existing wires, however there are just a bunch of blade connectors and I have no idea what is supposed to connect to what and how.  I'm attaching three pictures. One is the old motor/wires, the second is the inside of the new motor, and the third is really the only thing that alludes to how this should he hitched up. 3 & 2 were pre-connected out of the box...which leaves 4 & 1.  Is one of the wires from the light switch supposed to connect to 4 and one to 1?  If so, which one goes to which? Do I need to put blade connectors on the end of the wires that go down to the light switch in order to connect them?  Any help is much appreciated.
      
Hello,



I am replacing a bath light and I am a bit confused by the wiring. I can reattach the wires with the new fixture exactly like the old fixuture was attached but the old fixture did not have a ground connection.



Here is how the wires a



Two whites connected to each other but not to the fixture.

One white and one bare copper wire (I thought it was the ground) connected together and to the white wire of the ligh fixture

one black wire connected to the black wire of the light fixture



How to I connect the the fixture green wire in this configuration?



Thanks
      
I have an outdoor light fixture that I am trying to replace.  The house was built ten years ago.



When I removed the original lamp, I noticed one of the two leads was wired to the ground, and one was wired to the black wire, which is hot per my current sensor.  There are three wires in the box - black, ground (bare copper), and white or neutral, all from a single romex cable.  Unfortunately, I do not recall where the white was when I removed the original. 



I wired the new lamp per the instructions, something I have done many times before - black to black, white to white, and bare copper ground to ground.  Nothing.  The lamp and bulbs are brand new, and I have tried four separate bulbs.  I checked the black and neutral with my current sensor and with the switch on and the lamp installed this way, both show as hot. With the lamp not installed, the switch on, and the wires disconnected only the black shows as hot.  The switch is single pole, and appears to be wired correctly with a black to each screw on one side and a copper ground on the other.



Assuming the new fixture was bad, I reinstalled the old fixture correctly -  black to black, white to white, and bare copper ground to ground.  Still nothing. No light, and I confirmed the bulb is good by putting it in another lamp.   The only way to get it to light is to connect the neutral in the lamp to the bare copper ground.



I capped the wires, turned the circuit back on, and identified all the outlets, switches and fixtures on the same circuit.  I opened every one of them up (four lights and eight outlets) and found three (one switch and two fixtures in another room) where multiple commons connect.  All were properly connected.  My outlet tester shows all outlets as "correct".  I found no instances of grounds connected to commons or vice-versa.



Any ideas?  Is it proper to wire this thing the way I found it?



Thanks for any and all advice!
      
I have a 30amp wall socket in my garage, connected to two 20amp fuses in my garage sub box. I bought a 60 gallon air compressor rated 230v 15amp (non-reversible???). I am under the impression that I can use this compressor with the socket I have. The compressor did not come with a plug but did have the wires. One red, one green, one white. The plug I bought to the match the socket has instructions for one black wire (hot) one green (ground) and one white (neutral) I guess my question is, would the red wire be my hot wire? Does everything else sound ok?
      
I have installed several GFCI breakers and every one had the neutral wire connected to the light colored and white paint marked terminal.

However a friend gave me a Siemens QPF 120 breaker and the load Power is not marked. On the side of the breaker, the pigtail is marked Panel Neutral and the terminal above this is marked Load Neutral. The other terminal which I assume is for the Hot, has a white paint marking and the screw is only slightly darker then the other. The white paint has me confused.

How do I wire this breaker?
      
I have a LEM .35hp meat grinder that did not come with reverse. It is a PITA to use and not have reverse. It is a 120v 250w motor, w 2 caps. There is no schematic on the cover, so I have no idea what which wire goes to where. I plan on using a DPDT switch to reverse it. on-off-(on or mom) switch. I have attached pictures of the motor wiring.  White/black come in then go into motor. White comes out of motor then to larger cap, other wire from large cap goes to red (into motor). Red comes out of motor into smaller cap, second wire to small cab is blue going into motor.



http://i1086.photobucket.com/albums/...n/IMAG0021.jpg

http://i1086.photobucket.com/albums/...n/IMAG0020.jpg

http://i1086.photobucket.com/albums/...n/IMAG0022.jpg

Any help would be appreciated.
      
I am trying to install a SunSmart Digital Timer to my hall lightswitch (single pole). The timer has 5 wires: Black, White, Blue, Red, and Green. My switch box only has 3 wires: Black, White, and the bare ground wire. I connected the black to the black, white to white, and green to the bare ground. I have power to the timer but the light doesn't work. What should I do with the blue and red wires? Right now I have each capped off. Thanks.
      
Hello. I'm a new home owner and DIY-er. I have 3 fluorescent lights  in my basement. I just replaced the fixtures' older ballasts with new  T8 ballasts in the first two lights and they work fine. I am having  trouble with the third light's wiring to the ceiling. I cut and removed  the old ballast without paying much attention because I was able to wire  the first two lights without any problem. I connected the new ballast  to the bulb sockets in the fixture, just like I did with the first two  lights. When I went to connect the ballast's black and white power lines  to the ceiling lines, I was thrown off by a red wire, which I guess is  connected to the light switch.  In addition, this light is connected to  the one of the other fluorescent lights and both are controlled by the  switch. I have attached  pictures of how I have it wired.



The way I have it wired now,  the other light turns on and works fine when the switch is flipped.  However, this light has the bulb flicker and then not turn on. If anyone  can tell what I'm doing wrong from looking at the pictures, I'd  appreciate any help! Thanks!
      
wanted to get feeback on my crude wiring diagram i put together for my small bathroom remodel. does it appear to be sound or am i way off base??



details:



* 20A dedicated circuit

* 12/2 wiring

* outlet's will be GFCI

* double gang box will contain:

* timer unit for exhaust fan

* double switch for heat lamp and lights

* Ground wiring is not shown but each fixture/outlet/switch will be connected to ground wire

* by calculations, the 34cu box is fine for the number of conductors/size of wiring. per box specs could handle 15/12g wires.

* the scanner cut off the bottom part of the picture, the 2 lights on the right are fed from the same switch, neutral's connected together.



F = Exhaust Fan

L = Light

HL = Heat Lamp

T = Timer switch

S = Switch

H = Hot

N = Neutral

Wire Nuts are in the box connecting the pigtails



Thank you for your input.