Saving Money By Using 12 Awg On 15amp Circuits?

Would it be cost effective to use 12/2 wire to run 15amp circuits?



I read that using 12/2 wire instead of 14/2 wire on a 15amp circuit will reduce the energy loss from voltage drop over the distance travled. A 2% voltage drop



The book gives the example of 200 ft carrying 120volts on 14 AWG will drop 8 volts, with 12 AWG the loss would only be 3 volts. and then adds this "The apparent savings in initial cost by using undersize wire is soon offset by the cost of power wasted in the wires and by the reduction in efficiency of lamps, motors and so on."



the book is "Wiring Simplified" by H.P Richter
      


Similar Tutorials

How to Lay Sod - The Right Way!
   - Make sure the green side faces up! And, there are a few more steps if you want to ensure a nice looking lawn. Prepa ...
The Difference Between Volts, Amps, and Watts
   - This article explains the difference between Volts, Amps, and Watts in an easy-to-understand non-scientific way. T ...
Water is Leaking from the Toilet – What do I do? (How to replace the wax seal for a toilet.)
   - If there is water leaking from the toilet, you need to make sure that you know from where the water is leaking. Che ...


Similar Topics From Forums

We had a pipe disconnect above the downstairs bathroom and the ceiling just about came down, so I decided since it was a hedious looking space, that it was a sign from the gods: Reno time!



Im now at the wiring stage. Originally there was a junction box with a light fixture out one side and a single pole switch(no ground screw...grnd wire attached to the box)on  the other. Typical set up: white from switch marked "hot" or "black" at both ends, and spliced with the incoming power's black wire. Then remaining blacks are spliced together as are the remaining whites... grounded accordingly.



What Im trying to do now is add a GFCI receptical to the mix. But Im having some trouble figuring it all out. NOTE: light fixture is not installed yet, just the wire for it with the ends capped off with a wire nut on each of the wires (Wht/Black/Grnd)



First, whats in the walls: Circuits on a 15 AMP fuse with older (but not the oldest) 12/2 wire with a blue weaved fiber outside cover. Still looks to be in great shape. I've continued using newer, yellow (Lomex or Romex?) 12/2 from homedepot as I've read that you should not mix 14 and 12 together.

All that is on the cicuit is 3 pot lights with 65w bulbs, single bulb on the stairway and what ever goes in the bathroom, so from my math, there should be plenty of room left on the circuit.



What I've tried so far:

A: I spliced the "hot"/"black" white wire from the switch to the incoming power's black, like before. Then I spliced all remaining blacks together with a wire nut, then the same with all remaining whites and then all grounds (did not attach any grnd wire to the Junction box).



Result, Nothing. After switching on the power, I tested the GFCI with a voltage tester as well as the switch and got no read.



B: Undid everything, re-spliced all like to like: all blck together, all white together..etc.



Result: Fuse trips.



Im no electrician, which I imagine is blatantly obvious from the above post, but I am following a Homedepot wiring manual, its just that what Im trying to do is not really addressed in the book... at least not directly. So I've been trying to figure it out by reading every single page, but Im still at a loss.



I've attached a very basic diagram of what is there right now. Any advice would be most appreciated.

Thanks in advance,

John
      
I'm replacing my electric range with gas.  The electric has (I think) a four-wire #6 or #8 cable approx 60ft run with a 40a dual post breaker.  I say "I think" because the wire is behind everything else in the panel.  I see red/white/black wires, but no ground and I can't read the jacket.  Once I cut the main, i'll have a closer look. 



The gas range requires only a 15amp breaker. 

Can I simply replace the breaker with 15A and the 4 prong outlet with a Nema 5-15p?  I'd cap off both ends of the red wire.  Is there some sort of code that says I need to maintain the 40A circuit for a future stove?

Or is there some sort of transformer I can plug into the stove end and avoid all that hassel.  ?
      
Hi guys. I'm Dan, and I'm in Knoxville, TN. I know running power to a shed is a very common topic here. I've been doing tons of reading and feel pretty comfortable with the requirements, but I have two questions I haven't been able to find a clear answer to.



First, my situation: I'm having a 10x16 shed built in my backyard, to be used primarily as a woodshop. I need more than a single circuit, so I know I need a subpanel and two grounding rods at least 6' apart, bonded to the subpanel with #6 bare copper wire.



My house has 200 amp service, and the main panel is in the garage at the opposite corner of the house from where the shed will go, so it would be pretty inconvenient to run a feeder from, there. But there's an existing 100 amp subpanel in the basement, presumably installed when the previous owner finished the basement. I'll be running a 60 amp feeder from that subpanel to the shed.



My total run will be something like 75', so I'm running #6 THWN for the two hots and neutral, and #10 THWN for the ground. I plan to bury it in 1.25" schedule 40 PVC, buried 18" deep.



My first question relates to how I need to run the wire when it's not underground. The basement is finished with a drop ceiling, so I plan to run the feeder across the drop ceiling, out of the house, down to the ground (it's a walk-out basement), then underground the 26' to the shed. I assume it still needs to be in conduit for at least the part that runs up the wall of the house. But what about inside, when it runs through the drop ceiling to the panel? Does it need to be in conduit for the whole run? Or would I just staple the four wires to the joists or something?



The other question relates to the trench. I've got a rain gutter downspout that discharges right at where the shed will soon be, so I'm running a 40' length of 4" PVC to pipe that water past the shed. It will be buried just about 6-12", just enough to run under the shed. Can I run the power conduit in the same trench (obviously, deeper)? Presumably I'd dig the 18" trench to the shed, lay the schedule 40, then add a few inches of dirt to bring it up to about 12" deep, and extend the trench past the shed at that depth, then lay the 4" drain pipe and backfill. Or do I need to dig two separate trenches? Is there a rule about how far apart they need to be if so?



If anyone sees any other flaws or concerns with my plan, please do speak up, I want to do this right. Thanks!



Dan
      
Help!  We decided to raise the ceiling in our kitchen for some new taller cabinets. We have 30" cabinets with a 7' drop ceiling. By taking out the drop ceiling we can go to an 8' ceiling with 36" cabinets.  We just had the ceiling taken out and now I see I got a problem!



This is a 2 story home, the wall in question is a load bearing wall (runs through the center of the house) The main breaker panel is in this wall (the panel opening is in the adjacent family room)



As you can see in the photos I cannot extend the wall up because all of the home wiring is in the way!  I expected I might have to run longer wires but not this. 



Some ideas we've thought about...

notch the double 2x4s (not sure how much I need to notch or allowed to)



build a cove (box) and leave the wires like they are (might be an eyesore in our new kitchen)



put up a large crown moulding along the entire wall (would be the only crown moulding in the house)



extend the ceiling up 6-7" instead of 12" (should leave enough room for wire to stay)



I'm leaning to the notching option if I can find a way to reinforce that section.



Any ideas?



thanks!
      
I built a free standing garage with main power tapped from the home breaker box.  The contractor pulled 4 wires via a conduit to the freestanding garage panel which supplies lights, a garage door, and two 20 amp outlets.



Everything worked well initially, but about 1 week ago one section of the lights in the building went out.  The contractor came out and found that one of the two hot wires in the garage panel was only seeing 100 volts and that went down if anything else was turned on.  He swapped one of the ground wires for the bad hot wire and everything now works. 



What would cause a situation like this where the hot wire apparently had a voltage loss?  Is it safe to continue with the fix where the faulty wire is now the ground?



Thanks in advance!
      
I have a 2 story house, I just had the drop ceiling in the kitchen removed and it will be raised up 12".

Right above the kitchen is the master bedroom. When the new drywall goes up that space becomes inaccessible.



I assume I cannot install "new construction" type recessed lights in the kitchen?
      
I completed my whole house rewire last Fall (took 2 years and severely tested my wife's patience). I read 5 wiring books in the early stages but read Rex Cauldwell's Wiring a House with his above code suggestions near the end of the project and now im obsessing about some of the stuff I didnt do. What do you guys think of some of the suggestions, specifically,



1. Driving 8 ground rods and the wire must be continuous (I drove 4 but the #6 copper wire from the panel to rod 1 is 1 wire and the #6 wire from rod 1 through rod 4 is another wire but both are properly clampled to rod 1 with an acord clamp). Funny, even with 4 rods there is almost no current through the rods versus 2-3 amps through the traditional cold water pipe ground



2. 1 circuit for each duplex receptacle in bathrooms. Since I have a quad in each of the batchrooms, that would be 4 circuits instead of 1 (code allows an unlimited number of bathroom receptacles on one circuit which does seem odd)



3. Nothing shared with kitchen counter receptacles (ie kitchen wall and dining room on their own)



4. Dedicated circuits for everything - I added dedicted circuit for fridge, microwave and dishwasher/disposer, but did not separate the dishwasher disposer onto 2 circuits. There used to be what I called "Circuit X" which did kitchen counter, microwave, dishwasher, disposer, fridge, 2 kitchen counter outlets, dining room and 1 outside outlet. Wife frequently blew that one. Circuit X was divided into at least 5 circuits during the rewire



5. No switch loops - did 5 of these to save on carpentry/avoid certain box fill problems. Now 2011 code says no switch loops without a neutral. Oops?



Just wondering what you guys think.
      
I have a 30amp wall socket in my garage, connected to two 20amp fuses in my garage sub box. I bought a 60 gallon air compressor rated 230v 15amp (non-reversible???). I am under the impression that I can use this compressor with the socket I have. The compressor did not come with a plug but did have the wires. One red, one green, one white. The plug I bought to the match the socket has instructions for one black wire (hot) one green (ground) and one white (neutral) I guess my question is, would the red wire be my hot wire? Does everything else sound ok?
      
I am doing a bathroom remodel and have a 20 AMP circuit with only a single outlet and 12/2 wire.   I have two other outlets that are already wired with 14/2 wire.  I would like to put the outlets on the same circuit and wondering if it is okay to mix the 14/2 and 12/2 wires on the same circuit IF I swap out the breaker to a 15 AMP.  I've calculated the load and the 15 AMP would be sufficient.



I know I could not mix in the 14/2 on teh 20 AMP circuit but I believe it is okay to mix them on the 15AMP.
      
Is there anything that actually stops me from wiring a 2.8kW oven in 2.5mm twin and earth? Done the cable sizing calculation and voltage drop and it's all legit, am I missing something though? I know a few people have said it better to wire it in 4mm/6mm incase a differemt cooker etc is ever put in, but is it dangerous for it to be wired in 2.5 for example could the cable overheat?