Rough In Questions
I'm in the final stages of a rough in.... three questions:
1) Do the feeds to the panel need to be in the panel but not connected or is it ok to just have them pulled over by the panel 2) I've got can lights in a drop ceiling - do I just staple the cable to the joist in the area the light will go and coil up the excess? 3) I have an outlet and a switch that I can't disconnect right now(sump pump and a stairway light) but these will be going on new circuits I pulled. Obviously I can't get the box ready, can I just pull the cable and have it there by the existing box? I thought about putting in a new box, but there really is no space for the outlet and we like where the switch is. I'd call the inspector and ask his preference but it is a voicemail box that has been full for a week. Thanks. Similar Tutorials
How to Lay Sod - The Right Way!
- Make sure the green side faces up! And, there are a few more steps if you want to ensure a nice looking lawn. Prepa ...
The Difference Between Volts, Amps, and Watts
- This article explains the difference between Volts, Amps, and Watts in an easy-to-understand non-scientific way. T ...
Water is Leaking from the Toilet – What do I do? (How to replace the wax seal for a toilet.)
- If there is water leaking from the toilet, you need to make sure that you know from where the water is leaking. Che ... Similar Topics From Forums
I'm trying to figure out how exactly this should be redone... right now there is a NM cable going from the panel though the rim joist and outside straight down into the ground and out about 2 ft into the sump well then it jus dangles there with a female plug end connected to that which the sump pump then plugs into... well this actually shorted out the other night and created a wonderful noise and sparks...
how should I redo this? right now its not even GFIC... just straight into a 20 amp breaker... I was thinking put an outside receptical on the side of the house run that straight thorugh the back of it into the rim joist and to the panel... have the outlet on that a GFIC outlet then run a underground line from that to the pump using UF cable with a similar female plug end inside the well (the well is about 11 ft deep and the plug is about 1 ft from the top right now... then that would just plug into the GFIC outlet on the side of the house... that outlet would of course have one of those clear enclosures around it that is water tight... suggestions? comments? code violations?
Getting ready to replace my well jet pump with a 240 volt model (currently I use a 120 volt pump. Currently I have a 20 amp, 120 volt circuit that runs from the house to the pump house about 60 feet. I use that circuit for the pump, a light and a receptacle. I want to replace that circuit with a 20 amp MWBC using 12/3 UF cable from the sub panel in my detached barn to the pump house (about 20 feet).
Question: Can I use 1/2" seal-tite to run from the sub panel to a a junction box prior to going underground with the 12/3 UF? The seal-tight run would be about 30". (I have a bunch of seal-tite, connectors and #12 THWN that I bought cheap at a storage unit auction.) The seal-tite would be run in the stud bay and along side the ceiling joist to get from one side of the barn to the other. Question: Can I use an unfused air conditioning disconnect at the pump house to disconnect the 2 ungrounded conductors of the MWBC. I can find nothing in the NEC that would bar either of these items, but I am a code novice.
I'm preparing for finally calling in for my rough in inspection and was hoping I could get a checklist or at least some suggestions as to what work should and should not be completed for a rough-in inspection. Does any wiring need to be spliced, wire-nutted, terminated within the panel or lighting or receptacle boxes? My project was running power from main panel to lug and from lug to sub in detached res. garage and installing 4-5 lighting and recep circuits.
We are just beginning to start with our kitchen remodel. Today, I mapped out all the circuits and this is what I found.
Circuit # 7 - 20 amp circuit to 1 back splash outlet then to 3 kitchen wall outlets, then to a closet outlet and closet ceiling light and then to a side porch light! Circuit # 8 - 20 amp to Dishwasher and Disposal Circuit # 9 - 20 amp circuit to microwave and kitchen ceiling lights. 2 patio recessed lights and dining room ceiling light. Circuit # 12 - 20 amp circuit to another back splash outlet then to 2 dining room wall outlets. Circuit # 14 - 20 amp to Refrigerator only Circuit # 18 - 15 amp to GFCI outlet in garage then that feeds 3 outlets for 3 bathroom outlets and 1 outside patio outlet. I going to have to add 1 more back splash outlet due to increase in counter space. I'll put the microwave on a dedicated circuit. So I need 2 additional breakers but I only have 1 blank spot in the breaker panel. I guess I can add one of those slim tandem breakers. So my question, is it ok to have additional wall outlets on the same circuit as a back splash outlet? If it's ok I'll lighten up circuit # 7 by putting some of those wall outlets on the additional back splash outlet. Oh, I have 2 20 amp circuits I did not get identified yet! I'll get to those tomorrow. thanks!
I want to run Romex from a j-box, that is in the ceiling of my basement, to the main panel. I know that I can run Romex from the box along the face of the joist (not the bottom), but what are my options once the Romex gets to the wall? The joist I am using, conveniently enough, meets the wall ideally for where the panel is. However, I've read that I need to run the Romex through EMT, or some form of conduit.
If you look at the picture I've attached, the panel is mounted on a piece of plywood that extends out underneath the joist. Can I just staple the Romex to the plywood and then run it into the panel without using any conduit? The cast iron pipe makes using any conduit quite a problem. The cable you see is MC Lite, but I want to replace it with Romex. There are going to be up to 9 more lines coming into the panel this very way.
Greetings,
I am looking to wire a sub-panel in my barn to support a general workshop. Loads would include standard woodworking tools (including 220V table saw), welding, air compressor, etc. The house has 200AMP main breaker and minimal in-house loads. Dryer is gas, Oven and cooktop are gas. Water heater is off the oil furnace. I think the biggest single load is the well-pump and/or fridge compressor. We do have sporadic toaster oven, hairdryers etc. Otherwise its just lights, ceiling fans, flat-panel tv, stereo... We had 4" conduit installed to the barn, so there is plenty of room to pull a big cable. The entire run from the house panel to the barn totals around 155' (probably less, but rounding up) My questions a Can I pull a 100AMP sub-panel from my main house panel as described? Would 4/0,4/0,4/0,2/0 aluminum service entrance cable be a good choice for this run? Could I do it with something lighter? Could I put an additional sub-panel in the garage (about halfway to the barn) by interrupting the run? The garage subpanel would have a 220V plug for possible welding and/or electric car charging. Would this require a separate run? Are there any other considerations I should be thinking about in planning this? Thanks for any thoughts you can share on this! Cheers, pete
First off, I have read a majority of the posts concerning this subject and they have been very helpful and answered many questions, but I still have a few.
I am wanting to run power to a detached shed that is around 100 feet from the house. However, due to the location of my main panel and the easiest route to run the power, I am looking at running cable about 270 feet. I measured it out to exactly 263 feet, but figured it would be best to go longer. I am wanting to run at least 60 amps to the shed, as I won't be using it for nothing more then power outlets (basic power tools) and lights. Here are my questions: 1) What cable would be best for such a long distance run? 2) Would a 60 amp subpanel be sufficient for this job. I am looking at only 4 circuits: 1 for internal outlets, 1 for lighting, 1 for motion sensor light outside and 1 for external outlet. I am looking at the following panel: http://www.homedepot.com/Electrical-...&storeId=10051 I have seen some marked 70 amp and wondering if they make a difference: http://www.homedepot.com/Electrical-...&storeId=10051 3) Also, I will be installing a 30 amp RV connector circuit from my main panel to the where I park my Camper Trailer, which is a run of about 75 feet. What would be the best cable for this sort of run under ground? Can I run both cable together in the same conduit until I junction if off to where I will be installing the plug for the camper? 4) Would the following be the circuit breakers to use: 60 amp - http://www.homedepot.com/h_d1/N-5yc1...&storeId=10051 30 amp - http://www.homedepot.com/h_d1/N-5yc1...&storeId=10051 I think that is it for now. Thanks in advance for all your help!!
I am installing 200 amp residential service. From the meter socket I am doing a very short run into the crawlspace to a 200 amp fused disconnect switch. From the disconnect switch I am doing a 60 foot run to the 200 amp panel. The run between the disconnect and the panel is all within the crawlspace interior ( heated ). Do I have to use ACWU cable or is there a cheaper alternative? I also need to isolate the bonding so is 4 wire configuration very common ? This is a Canadian question specific to British Columbia codes.
Hey everyone - question about home wiring that was done when the house was built about 20 years ago (which putting it delicately...is very shoddy at best). I'd like to think of myself as fairly knowledgeable in basic home wiring...but this one has me baffled and I really hope someone can help.
I am redoing a screened-in porch at the back of our house. There is currently a working outlet, and single-pole switch that turns on an outside bug zapper, and a wire running coming into a second switch...then leading into nothing in the ceiling (presumably for a future ceiling fan / light install that was never completed). I gutted the entire porch and using one of those audible voltage testers, discovered the wire than ran into the second switch / ceiling box did NOT work. Not thinking much about it, I tried figuring out how the first switch (to that outdoor bug zapper) was wired. Most of the wiring for that switch and the outlet I mentioned is behind the plywood sheathing of the house...so it's near impossible to figure out where it goes. Initially it LOOKED like the power from the circuit panel came into the outlet first...and then went out to the bug zapper switch. (Why did I think this? The outlet had a B/W wire coming into it...and another B/W going out back into the wall somewhere. Tracing that wire along the basement foundation best I could...it looked like it went right into the bug zapper switch). So wanting to completely eliminate the bug zapper switch, I disconnected all of the wires that were connected to the outlet to figure out which set was leading to it. Here's where I got confused. When I did this and re-tested voltage at the outlet, one set of wires was live...and the other set was dead. And that makes perfect sense. Yet the bug zapper switch STILL worked. OK - so my conclusion: the power for this bug zapper switch isn't coming from the outlet. No problem. But just because I was near it, I decided to also check that 2nd switch / ceiling wire combo...and what do you know - it was LIVE! I got super excited it was working but then super baffled because I didn't do anything to that ceiling wire at all. In fact - all I did was DISconnect 2 sets of wires at a nearby outlet. Confused but happy, I was ready to pack it in for the evening and re-connected the incoming / outgoing wires back to the power outlet. Flipped the circuit breaker on. No issues. BUT - now all of a sudden the 2nd switch / ceiling wire that magically started working was NO longer working - just like it hadn't been since I started this whole process. Logic is telling me it's obviously got something to do with the outlet wiring...since that's the only thing I messed with. But why would the ceiling wire all of a sudden become LIVE when the wires going into the outlet were all disconnected? It's certainly a first for me. Can anyone help me figure this mystery out? Thanks gang!
Hello,
I currently have one light switch which operates an outlet in one of my bedrooms. I want to add a ceiling fan that has independent switches for the fan and light - but I want to make sure i'm wiring it correctly and safely. Current (First Pic)- Live hot feeds into bottom of switch (bottom insert hole) and the all of the bedroom outlets (pig-tailed) tie into the bottom of the switch on the screw. Coming out of the top of the switch is one hot which feeds to a single outlet. All of the neutral and grounds are tied together. New Plan (Second Pic)- Remove the constant outlet hot from the screw, add a new hot wire to the top of new switch and run a wire up to the attic for fan. Add another hot wire from the bottom of that switch to the third switch and run another wire up to the attic for the lights. Re-connect the constant outlet wire to the screw of the last switch. Connect all the neutrals and all of the grounds together. At the top of the ceiling, connect the neutrals and grounds together with the fans neutral and ground. Connect the fan hot to the fan switch hot, and the fan light hot to the light switch hot. |