How Important Is It For A Wine Fridge Have A "dedicated Outlet?"

I am thinking of purchasing a WineKoolr used but after looking at the manual online it states that it must be plugged into a "Dedicated separately fused, grounded, 15 amp 100-120v line." The price I can get this at is awesome, but I live in apartment and am not sure, but think I only have 1 dedicated line at all, for the fridge. The previous owners said they just had it plugged into a normal outlet fine, but I want to know if it is a serious issue to do this? I really want a nice cooler for my beer cellar since I have no actual basement, so I am really hoping I can make this work in my home. Thanks for any help!





*Someone asked me on another forum what breakers I have for where I want to install it, and its in my second bedroom.  The breaker for those outlets is a 15A.  They also said that it probably says that in the manual to cover themselves legally but I should likely be just fine.





**

Well I turned off the breakers until I found which was for the outlets in the spare room.  As far as I can tell, the only things on this circuit are the spare bedroom outlets (not the lights), and 1 outlet in the hallway.  Nothing is plugged into any of these and its a 20A circuit.
      


Similar Tutorials

How to Lay Sod - The Right Way!
   - Make sure the green side faces up! And, there are a few more steps if you want to ensure a nice looking lawn. Prepa ...
The Difference Between Volts, Amps, and Watts
   - This article explains the difference between Volts, Amps, and Watts in an easy-to-understand non-scientific way. T ...
Water is Leaking from the Toilet – What do I do? (How to replace the wax seal for a toilet.)
   - If there is water leaking from the toilet, you need to make sure that you know from where the water is leaking. Che ...


Similar Topics From Forums

I posted this in the woodworking forum and I got a ton of rants so please spare me that please. I'm not an idiot and I intend on completely turning off all power before attempting anything.



So I've been researching adding a couple of electrical outlets to my garage (where the panel is). I want to run a new 120v outlet for the tablesaw (older craftsman 113 series) so that it is on it's own circuit and a 240v outlet for a grizzly G1029z2 DC on it's own circuit as well.



What amp 120 circuit should I add for my tablesaw? Will a standard 15a breaker be fine?



What amp 240 circuit should I add for my DC? The motor plate states 12 amps and the manual says the electrical is a minimum circuit size of 20. Should I just install a 20amp circuit or go with larger circuit?



Need recommendations on the gauge of wire to use on each circuit.
      
OK, I'm an electrical dummy ...



I have finished basement w/a bathroom. We have an ejector pump off the bathroom that has been plugged into an outlet w/gfi since I've owned the house (10 years). There is also a booster fan for my electric dryer plugged into the outlet (has been the same for 10 years).  The only thing that has ever tripped up that outlet is using a hair buzzer in another outlet within the bathroom (but once you hit the reset its fine).

   

  This morning I realize the ejector pump was not sucking down the water from the drains. I looked at the outlet and realized it needed to be reset. When I reset it, the pump would run for a few seconds and the outlet would trip up again. Tried this a few times. Thought maybe it was an issue w/the outlet altogether. Neighbor suggested maybe it was an issue with the pump. Went thru various scenarios and bottom line is when I plug the pump into other outlets it works totally fine and once I do that and reset the outlet it was on, the booster fan works fine and the outlet does not trip. So, basically this outlet is tripping when the pump is on it but the pump is not tripping other outlets and the outlet works fine as long as the pump is not on it.

   

  What could be causing this? Why would an outlet that housed the two things on it all of a sudden continue to trip when the pump is on it but the pump is fine on its own in another outlet and the outlet is fine on its own w/o the pump?
      
I have a 1960s house with EMT throughout. 



I recently replaced 2 florecent fixtures in my basement with 4 LED lights in their own J-Boxes in the drop ceiling. I did the following:



1. Rerouted the the conduit from the light switch to the main j-box for the lights. (previously it was going directly into the fixture) 

2. Ran 4 foot whips to each jbox holding the LED (metalic 14# wires)

3. Cut the old spliced wire (that was just twisted and taped) and used a wire nut

4. Replaced the switch with a dimmer



The lights work great.  Noticebale improvement and the dimmer is excellent.



The issue is that the circuit for the kitchen is now tripping.  I told my wife its just a coincidence, but she is sure I caused it.  Its only happened 2x (1 day apart.  Nothing unusual running on the circuit, only the fridge and the gas stove which as not in use)



Can my "new" work possibly impact another circuit?   What should I check?  Any way to avoid re-doing my work?



Things I noticed / may or may not be relevant:

1. Some of the EMT is directly in contact with a copper water pipe

2. The switch / dimmer isn't grounded

3. The wires in the jbox were nasty and old.  There was corrosion on the jackets and the jbox.  Looks like some water leaked down fromt the laundy above at some point in the last 40 years.

4. At some point (months ago) when I was in the basement I touched some of the EMT and something that was plugged in I swear I feld a shock. (just listing everything I can think of).  I didn't think much of it at the time, but now my whole electrical system is suspect.

5.  The tripped circuit (fridge, MW, stove) didn't appear to be tripped.  The fridge wasn't on.  When I turned off and back on the circuit the aplliances came back to life.  Appliances less than 1 year old. 

6. The clock on the range was reset at one point but I didn't think I turned on or off the circuit.  The lights for the basement were switced off but still worked with the fridge circuit tripped.

7.  We had a huge electrical storm right before I did the work

8.  We have a "stablock" panel that the home inspector got all bent out of shape about.  Other than truning on and off breakers I have never touched it.

9.  Kitchen breaker and basement light breaker are adjacent in the box

10.  I believe kitchen and basement share the same EMT in places.

11.  I think I now have too many connectors in my j-box.  Will likely add an extension.

12.  I didn't use the red "bushing" on all my whips as I ran out of them, but I was careful with the metal sheath and really don't think any wires were cut. (besides if there was a short wouldn't my LED lights fail and that circut break?)



HELP.  I am happy to call a contractor to come in, but I don't have an electrician I trust yet and I'm scared bringing someone in before I isolate the problem a little.
      
I have a mwbc where one is running my kitchen outlets, and the other is running a dedicated circuit for the disposal. the breakers are adjacent in the panel, so they are on opposite phase and share a common neutral and ground. I was updating the outlets and so turned off only one of the breakers. when I tested the line to make sure it was off, my voltmeter still read about 10 volts. Is this normal? there were no appliances connected to either circuit.
      
Going through a crazy heat wave here in SoCal, and one of my tenants called to tell me that the electricity isn't on in some of his rooms. He turned on his portable AC unit that he has been using all summer and something may have happened.



Downstairs:The dining room light switch, downstairs light switch do not work. All outlets around them do work though, which is odd cause I would have thought they'd be on the same circuit.



Upstairs: The side bathroom light switch does not work, but outlets all work. In the master bedroom (where the AC unit is located), the master bathroom light switch does not work, nor does the master bedroom light switch. All of the outlets do not work either. I used my outlet tester and it gave me the hot/ground reversed lights. I think this means that the white/black wires are reversed on the outlets (has not changed recently).



I went over, checked all of the breakers. Switched them to off, then back on, did not fix the issue. All breakers stay in the on position without tripping, so no shorts?



Checked all GFCI's, hit test, then reset, did not solve the problem.



We unplugged everything from all outlets, and retried, but it didn't work.



I checked continuity between the main power lines, and the output of the circuit breakers, and all were fine. I did NOT check the voltages though, and will do so in the morning when I stop by again.



Is there anything else I should check?
      
Hello all.  I'm new on the forums and new to electricial.  I bought a house recently and found some outdoor outlets that don't work.  Only one does.  I've searched the forums and found some troubleshooting steps such as reset all the GFI outlets in house, but that didn't resolve the issue.  None of the outdoor outlets are GFI (they don't have a button).  I only have one circuit breaker and I've looked around and didn't find a second one.  None of the circuit breakers are label for the outdoor outlets and they are all in the "on" position.  All the indoor outlets work fine.  What other troubleshooting steps can I do before forking out $$ for an electrician?  Thanks!
      
hi...



my electrician walked out on me because i asked him to itemize everything since i wasn't happy about his "extras" that he's charging me for...  i already paid him $9500 of the original $10k bid but he only finished about 80% of the work...



there were a number of extras that he recommended as well as some that i requested...  he decided to jack up the bid to $16.3k...  which included a charge of $1650 for cat6 wiring to 6 locations, $500 for a dedicated 15a circuit for a whirlpool bath...  there were 7 more switches, 13 more receptacles, 5 more recessed lights, 16 more lighting locations and 1 more smoke detector...  is that $6k worth of "extras"?



anyway, i've decided to go with someone else to finish up but so far nobody wants to finish up others' work...  worst case i'm thinking is i'll do it myself...  i already wired a 15a dedicated circuit for my whirlpool tub with no issues so i think i'm up to the challenge...



i just need some guidance to make sure i don't electrocute myself...



here's a photo of the panel...  what's going in the circled area?





also, other than the hots not being connected to the breakers (for the most part) does anyone see anything amiss with this panel?





thanks
      
We are just beginning to start with our kitchen remodel. Today, I mapped out all the circuits and this is what I found.



Circuit # 7 - 20 amp circuit to 1 back splash outlet then to 3 kitchen wall outlets, then to a closet outlet and closet ceiling light and then to a side  porch light!



Circuit # 8 - 20 amp to Dishwasher and Disposal



Circuit # 9 - 20 amp circuit to microwave and kitchen ceiling lights. 2 patio recessed lights and dining room ceiling light.



Circuit # 12 - 20 amp circuit to another back splash outlet then to 2 dining room wall outlets.



Circuit # 14 - 20 amp to Refrigerator only



Circuit # 18 - 15 amp to GFCI outlet in garage then that feeds 3 outlets for 3 bathroom outlets and 1 outside patio outlet.



I going to have to add 1 more back splash outlet due to increase in counter space. I'll put the microwave on a dedicated circuit. So I need 2 additional breakers but I only have 1 blank spot in the breaker panel. I guess I can add one of those slim tandem breakers.



So my question, is it ok to have additional wall outlets on the same circuit as a back splash outlet?  If it's ok I'll lighten up circuit # 7 by putting some of those wall outlets on the additional back splash outlet.

Oh, I have 2 20 amp circuits I did not get identified yet! I'll get to those tomorrow.



thanks!
      
I'm trying to fix a problem with a track light installment over the a bar I've just put in. I've done it before. never had issues. but this particular problem is driving me nuts. It just defies logic.  The electrician who actually installed the associated dimmer switches with this dining room area was called as it seems it may be a flaw with his wiring, but he's blown us off and I have to try and solve this myself.



This is how it's all set up. I've been rehabbing our home from top to bottom, and converted our old kitchen into a dining area. Within this dining area are four sets of lights, all controlled from one box containing four dimmer switches. I set up all the new wiring and installation of the lights in the ceiling, and we paid an electrician to come in, check everything out, set up the multiple switches, and connect it all to the board. It's all new copper wiring from beginning to end, as I didn't want to connect or splice in to the old aluminum wiring that was in place. All the new wiring and lights are on a dedicated 15 amp breaker. Three of the sets of lights were set up to be available from the day the electrician came around. The fourth, for the track light over the bar, was left hanging from the ceiling capped off and with the switch off, as I still had work to do installing an overhead wine rack, under which the track was going to be set.



Two days ago I finally got around to putting the track up, but after setting it in place and connecting the power up the lights wouldn't work. I took the lights out to our kitchen, where I installed another track light system some time ago, plugged one of the lights in, and it worked just fine. I then went back to the bar area and used a spare track, then a spare connector, to see if I could isolate the fault, yet neither of the items provided a solution. Now here's the weird bit - every time I tried checking the system out, I'd get 120 volts showing from the wiring and from the track when I'd test with the multimeter. But the second I'd put a light into the track, the multimeter would drop to zero on the voltage reading on either the wiring or the track. Take the light fixture back out, and the voltage would pop back up. Inserting the light was thus completing some kind of odd loop. It wasn't just one light - I double checked by grabbing working lights from the kitchen track and inserting them into the other track - the same problem would pop up. Finally, having come to the conclusion that there was nothing wrong with the track at all, I took the whole assembly over to a nearby wall outlet, used some spare electric cable to connect up to the appropriate slots - presto, the light came on! I even double checked all this by grabbing another light fixture destined for our bathroom, and tried connecting it to the wiring over the bar. Nothing. Yet as with the track light, the minute I took it over to the wall outlet and connected it, the light worked.



So everything logically points to the fact it has to be something to do with this individual circuit, right, because a) the light fixtures work when plugged into another circuit and b) the other three dimmers and lights hooked up in the same box work fine and draw power from the same wire cable/breaker combination. The only things left that I can think of is that the electrician has either wired the dimmer switch up incorrectly or that there's some kind of flaw inside the switch itself. Does this make sense?



A friend also told me to double-check to make sure that the black wire feeding power to the light was indeed the hot wire, and it is.  If I touch it with the black test lead from the multimeter and put the red one to the neutral I show 120 volts. If I keep the black test lead on the black wire and put the red test lead to the ground - I also show 120 volts.



A final point. I know I'm not overloading the circuit - not even close. With all four dimmers maxed and every light on - including the test light on the track - I'd only be drawing 8 amps on a 15 amp breaker, besides which I'm only using one set of lights while I'm working on this problem anyway. This is a dedicated circuit, so there's no additional power being drawn away by something else.



So how am I getting 120 volts from this wiring, according to my multimeter, yet it won't light up ANYTHING and keeps giving off the indication that some kind of loop or short is being created every time I actually plug a light into the track? It's got me totally stumped.



Anyone have any ideas?
      
Hello.



I recently purchased a home that has a a new grounded breaker panel but none of the outlets themselves are grounded save the hvac system in the basement. I had an electrician come and he said the fastest way to get it done is to switch the appropriate breakers to GFCI breakers in my service box and then I can change the outlets and then just put the stickers that say ungrounded etc on the new 3 prong receptacles. he called the inspector to double check and the inspector told him that he can't do it this way but he needs to find the first outlet in the loop from each breaker line and change that receptacle to a gfci and then we can change each receptacle to 3 prong in that loop.



Wouldn't just changing the breaker do the same thing? also if I did just install a Gfci receptacle on the first outlet in the loop, if it breaks wouldn't the rest of the outlets behind that gfci not function until I replaced the Gfci outlet where as a breaker would just pop and I can simply go turn it back on?



Just wanted to get some opinion from the experts as I'm willing to spend more on doing gfci breakers and am confused as to why the inspector suggested the way he did



Thanks for any help!