14 Gage Connected To 12 Gage

can a 14 gage wire for a light be connected to a 12 gage wire?  the breaker is 20 AMP.



there is no light in a room with an outlet present, i was going to put in lights and hook up the lights with 14 gage to the 12 gage wire connecting the outlet.



or, should i be consistent and use 12 gage to connect the light?



thanks fella's
      


Similar Tutorials

How to Lay Sod - The Right Way!
   - Make sure the green side faces up! And, there are a few more steps if you want to ensure a nice looking lawn. Prepa ...
The Difference Between Volts, Amps, and Watts
   - This article explains the difference between Volts, Amps, and Watts in an easy-to-understand non-scientific way. T ...
Water is Leaking from the Toilet – What do I do? (How to replace the wax seal for a toilet.)
   - If there is water leaking from the toilet, you need to make sure that you know from where the water is leaking. Che ...


Similar Topics From Forums

I am going to install some can lights throughout the house soon.  I have one light in the center of each room that is already wired up.  I will be patching the existing light boxes up to run the new can lights, utilizing the wiring that is already present. 



When hooking the extra lights up should I use 12/2 or 14/2 wire for running them in parallel?  There will probably be no more than 3 or 4 can lights per room ran with CFLs.  The current lights that are in each room take up to 3 bulbs per fixture.
      
Hello. I'm a new home owner and DIY-er. I have 3 fluorescent lights  in my basement. I just replaced the fixtures' older ballasts with new  T8 ballasts in the first two lights and they work fine. I am having  trouble with the third light's wiring to the ceiling. I cut and removed  the old ballast without paying much attention because I was able to wire  the first two lights without any problem. I connected the new ballast  to the bulb sockets in the fixture, just like I did with the first two  lights. When I went to connect the ballast's black and white power lines  to the ceiling lines, I was thrown off by a red wire, which I guess is  connected to the light switch.  In addition, this light is connected to  the one of the other fluorescent lights and both are controlled by the  switch. I have attached  pictures of how I have it wired.



The way I have it wired now,  the other light turns on and works fine when the switch is flipped.  However, this light has the bulb flicker and then not turn on. If anyone  can tell what I'm doing wrong from looking at the pictures, I'd  appreciate any help! Thanks!
      
wanted to get feeback on my crude wiring diagram i put together for my small bathroom remodel. does it appear to be sound or am i way off base??



details:



* 20A dedicated circuit

* 12/2 wiring

* outlet's will be GFCI

* double gang box will contain:

* timer unit for exhaust fan

* double switch for heat lamp and lights

* Ground wiring is not shown but each fixture/outlet/switch will be connected to ground wire

* by calculations, the 34cu box is fine for the number of conductors/size of wiring. per box specs could handle 15/12g wires.

* the scanner cut off the bottom part of the picture, the 2 lights on the right are fed from the same switch, neutral's connected together.



F = Exhaust Fan

L = Light

HL = Heat Lamp

T = Timer switch

S = Switch

H = Hot

N = Neutral

Wire Nuts are in the box connecting the pigtails



Thank you for your input.
      
Hello,



I currently have one light switch which operates an outlet in one of my bedrooms.  I want to add a ceiling fan that has independent switches for the fan and light - but I want to make sure i'm wiring it correctly and safely.



Current (First Pic)- Live hot feeds into bottom of switch (bottom insert hole) and the all of the bedroom outlets (pig-tailed) tie into the bottom of the switch on the screw.  Coming out of the top of the switch is one hot which feeds to a single outlet.  All of the neutral and grounds are tied together.



New Plan (Second Pic)- Remove the constant outlet hot from the screw, add a new hot wire to the top of new switch and run a wire up to the attic for fan.  Add another hot wire from the bottom of that switch to the third switch and run another wire up to the attic for the lights.  Re-connect the constant outlet wire to the screw of the last switch.  Connect all the neutrals and all of the grounds together.



At the top of the ceiling, connect the neutrals and grounds together with the fans neutral and ground.  Connect the fan hot to the fan switch hot, and the fan light hot to the light switch hot.
      
I'm trying to fix a problem with a track light installment over the a bar I've just put in. I've done it before. never had issues. but this particular problem is driving me nuts. It just defies logic.  The electrician who actually installed the associated dimmer switches with this dining room area was called as it seems it may be a flaw with his wiring, but he's blown us off and I have to try and solve this myself.



This is how it's all set up. I've been rehabbing our home from top to bottom, and converted our old kitchen into a dining area. Within this dining area are four sets of lights, all controlled from one box containing four dimmer switches. I set up all the new wiring and installation of the lights in the ceiling, and we paid an electrician to come in, check everything out, set up the multiple switches, and connect it all to the board. It's all new copper wiring from beginning to end, as I didn't want to connect or splice in to the old aluminum wiring that was in place. All the new wiring and lights are on a dedicated 15 amp breaker. Three of the sets of lights were set up to be available from the day the electrician came around. The fourth, for the track light over the bar, was left hanging from the ceiling capped off and with the switch off, as I still had work to do installing an overhead wine rack, under which the track was going to be set.



Two days ago I finally got around to putting the track up, but after setting it in place and connecting the power up the lights wouldn't work. I took the lights out to our kitchen, where I installed another track light system some time ago, plugged one of the lights in, and it worked just fine. I then went back to the bar area and used a spare track, then a spare connector, to see if I could isolate the fault, yet neither of the items provided a solution. Now here's the weird bit - every time I tried checking the system out, I'd get 120 volts showing from the wiring and from the track when I'd test with the multimeter. But the second I'd put a light into the track, the multimeter would drop to zero on the voltage reading on either the wiring or the track. Take the light fixture back out, and the voltage would pop back up. Inserting the light was thus completing some kind of odd loop. It wasn't just one light - I double checked by grabbing working lights from the kitchen track and inserting them into the other track - the same problem would pop up. Finally, having come to the conclusion that there was nothing wrong with the track at all, I took the whole assembly over to a nearby wall outlet, used some spare electric cable to connect up to the appropriate slots - presto, the light came on! I even double checked all this by grabbing another light fixture destined for our bathroom, and tried connecting it to the wiring over the bar. Nothing. Yet as with the track light, the minute I took it over to the wall outlet and connected it, the light worked.



So everything logically points to the fact it has to be something to do with this individual circuit, right, because a) the light fixtures work when plugged into another circuit and b) the other three dimmers and lights hooked up in the same box work fine and draw power from the same wire cable/breaker combination. The only things left that I can think of is that the electrician has either wired the dimmer switch up incorrectly or that there's some kind of flaw inside the switch itself. Does this make sense?



A friend also told me to double-check to make sure that the black wire feeding power to the light was indeed the hot wire, and it is.  If I touch it with the black test lead from the multimeter and put the red one to the neutral I show 120 volts. If I keep the black test lead on the black wire and put the red test lead to the ground - I also show 120 volts.



A final point. I know I'm not overloading the circuit - not even close. With all four dimmers maxed and every light on - including the test light on the track - I'd only be drawing 8 amps on a 15 amp breaker, besides which I'm only using one set of lights while I'm working on this problem anyway. This is a dedicated circuit, so there's no additional power being drawn away by something else.



So how am I getting 120 volts from this wiring, according to my multimeter, yet it won't light up ANYTHING and keeps giving off the indication that some kind of loop or short is being created every time I actually plug a light into the track? It's got me totally stumped.



Anyone have any ideas?
      
Hi, I have a fluorescent light I'd like to remove and add a tracklight.



Luckily it's in the basement with an unfinished ceiling.



here's the circuit map as is now:



1. breaker to fluorescent light.... connections inside

2. fluorescent light to switch at the top of the stairs

3. switch to the light in the stairwell. This terminates the circuit.



The wiring is all 14/2



I'd like to replace the the fluorescent light with a track light, but I'm not sure how to continue the circuit to the switch in the stairwell.



Is it safe to...



1. bring the cable from the breaker to the junction box.

2. connect the black wire with the black wire on the light AND the black wire leaving the box to the switch in the stairwell using a marette.

3. connect the white wire with the white wire on the light AND the white wire leaving the box to the switch in the stairwell using a marette

4. connecting a 6 inch bare 14 gauge wire to the box ground screw, then using a marette, connecting it with the ground wire from the cable entering the box as well as the one leaving and also the ground wire from the light.



Will this work and is it safe?
      
I am working on fixing an issue with the wiring in one of the bedrooms in my older mountain home. Though I was not present for the cause of the problem, here is what was told to me by the tennant.  he claimed that he went to turn on the light in the closet, (a 3 lamp track bar light, wired to a switch) he heard a loud pop from the light in the closet and lost power to to the room. The room has 6 recessed ceiling lights on 2 separate switches, presently only half of the lights work.There are no breakers tripped, no obvious shorts at outlets. I have opened the drywall following the wires around hoping to find a short but I have found nothing. I decided to try something, and I bridged the working switch to a dead outlet and everything turned on. I am waiting til the daytime to follow the wires outside to the breaker box, but so far no breaks or anything.. curious if anyone has any pointers.. could the pop he heard from the track lighting have killed a breaker? its about the only thing left.
      
Hello,



I am replacing a bath light and I am a bit confused by the wiring. I can reattach the wires with the new fixture exactly like the old fixuture was attached but the old fixture did not have a ground connection.



Here is how the wires a



Two whites connected to each other but not to the fixture.

One white and one bare copper wire (I thought it was the ground) connected together and to the white wire of the ligh fixture

one black wire connected to the black wire of the light fixture



How to I connect the the fixture green wire in this configuration?



Thanks
      
I'm wiring two lights to one switch with power coming into the switch. All the diagrams I see show the connection of the two lights at one of the lights(if that makes sense). Can all of the connections be made at the switch box if theres room? Basically a wire from each light and the power wire all run to the switch box and connected.
      
Hi, I have a problem where if I turn off my light switch on one side of the  room, it turns off anything plugged into the electrical outlet on the  other side of the room. For some reason, they originally wired that  outlet on the same circuit as the light switch. I would like to wire the  outlet so that it does not switch off whenever you switch off the light  on the opposite wall.



How do I go about doing that? Thanks.



(p.s. There are just the basic three wires in the electrical outlet; black/white/bare copper ground).