Supposed 3-way Switch
When repairing a light switch I came across this wiring in a supposed 3-way setting in my kitchen. Two Single Pole Double Throw switches controlling a single light fixture.
Check out the quick and dirty wiring diagram showing the way these are connected. I believe there should be a 14/3 between the two switches right? All I see is 14/2 coming in and a 14/2 going across to the other switch, and then a 14/2 going to the light. And why are the neutrals cut and wire capped? This doesn't make sense to me, but the light does work from both switches. Any insight will be greatly appreciated. Cheers! Similar Tutorials
How to Lay Sod - The Right Way!
- Make sure the green side faces up! And, there are a few more steps if you want to ensure a nice looking lawn. Prepa ...
The Difference Between Volts, Amps, and Watts
- This article explains the difference between Volts, Amps, and Watts in an easy-to-understand non-scientific way. T ...
Water is Leaking from the Toilet – What do I do? (How to replace the wax seal for a toilet.)
- If there is water leaking from the toilet, you need to make sure that you know from where the water is leaking. Che ... Similar Topics From Forums
Hi All,
Need to replace an old faulty two switch fixture in the bathroom (light and exhaust fan). Right now, each switch on the single fixture separately operates either the light or the fan, regardless of the position of the other switch. Want to keep things that way. Here is a picture of the old fixture's wiring: http://dl.dropbox.com/u/1179096/photo1.jpg To replace this fixture, I bought to the Leviton 5634 (design diagram he http://communities.leviton.com/servl...224%205634.pdf) Unfortunately, what is confusing me is the the different designs between the two fixtures and the fact that the original unit seems to have some kind of patch or cross over type wire connecting the top and the bottom switches (see photo link above). Any help/advice on how to wire this new fixture based on the picture of the current wiring configuration would be greatly appreciated. Thank you!!!
hello
I am dealing with what seems like a strange issue with a single pole switch, and I am royally baffled even after reaching out to someone a little more knowledgeable than me. Yesterday: Replaced with a single pole switch with an identical one that I painted (for decor reasons). Two wires were going into the old, and the same 2 wires are attached to the new one. However, the light it controls fails to come on despite light bulb being good, and outlet located 4 feet below the switch fails to operate. With voltmeter in hand I tested voltages. At the switch: 3 wires feed into it, all whites capped together, and 2 of the 3 blacks (A,B,C) are hot with 110. A is hot and was/is connected to one of the terminals of the single pole switch. B and C (hot) are capped together with a jumper that goes to the other terminal of the single pole switch. So I am royally baffled as to why a switch would be wired with 2 hot wires going into it. I swear it has been like that since we bought the house a year ago, and the light worked fine. I simply replaced the switch with the same wiring, and now it doesnt work. I even touched both hots (A and C) independently to wire B which (using common sense) should be the load wire to the lamp, but the lamp did not come one. Other outlets in that circuit do not work either. They get 110 to line and ground, but not across the outlet. I hope I was clear in explaining, and I hope someone can possibly shed some light so I can resolve this. Thank you
Im replacing what I thought was 2 single pole light switches but there is 3 black wires and one red. I hooked them up to the new switches but both switches worked the one light can anyone tell me how to connect the wiring?
Scratching my head on this. New pole building. For now, I want to use one circuit for the lights. What I'm trying to do, is, at one door, I have a 3 way, switching two flourescent lights. Also in that 4-gang light switch, is run a light over the door on the outside, and a light over the overhead service door, and another light over the door, on the inside. So 1 3way, and three single pole switches. At the back door, the other 3 way for the same two lights, and a light over the door on the outside, and another light over the door on the inside. I have the power from the m/p, going into the light box nearest the M/P. Long story short, instead of how I have it, which operates all the lights, as long as one of the three ways are on. If someone could help me with how it should be. I am using 12-3 from the switches. Using 12-2 from the first light box, to the second. I have a another 12-2 running into each switch box, to supply power for the single pole switches.
Thanks for any/all input.
Hello,
I currently have one light switch which operates an outlet in one of my bedrooms. I want to add a ceiling fan that has independent switches for the fan and light - but I want to make sure i'm wiring it correctly and safely. Current (First Pic)- Live hot feeds into bottom of switch (bottom insert hole) and the all of the bedroom outlets (pig-tailed) tie into the bottom of the switch on the screw. Coming out of the top of the switch is one hot which feeds to a single outlet. All of the neutral and grounds are tied together. New Plan (Second Pic)- Remove the constant outlet hot from the screw, add a new hot wire to the top of new switch and run a wire up to the attic for fan. Add another hot wire from the bottom of that switch to the third switch and run another wire up to the attic for the lights. Re-connect the constant outlet wire to the screw of the last switch. Connect all the neutrals and all of the grounds together. At the top of the ceiling, connect the neutrals and grounds together with the fans neutral and ground. Connect the fan hot to the fan switch hot, and the fan light hot to the light switch hot.
I'm trying to fix a problem with a track light installment over the a bar I've just put in. I've done it before. never had issues. but this particular problem is driving me nuts. It just defies logic. The electrician who actually installed the associated dimmer switches with this dining room area was called as it seems it may be a flaw with his wiring, but he's blown us off and I have to try and solve this myself.
This is how it's all set up. I've been rehabbing our home from top to bottom, and converted our old kitchen into a dining area. Within this dining area are four sets of lights, all controlled from one box containing four dimmer switches. I set up all the new wiring and installation of the lights in the ceiling, and we paid an electrician to come in, check everything out, set up the multiple switches, and connect it all to the board. It's all new copper wiring from beginning to end, as I didn't want to connect or splice in to the old aluminum wiring that was in place. All the new wiring and lights are on a dedicated 15 amp breaker. Three of the sets of lights were set up to be available from the day the electrician came around. The fourth, for the track light over the bar, was left hanging from the ceiling capped off and with the switch off, as I still had work to do installing an overhead wine rack, under which the track was going to be set. Two days ago I finally got around to putting the track up, but after setting it in place and connecting the power up the lights wouldn't work. I took the lights out to our kitchen, where I installed another track light system some time ago, plugged one of the lights in, and it worked just fine. I then went back to the bar area and used a spare track, then a spare connector, to see if I could isolate the fault, yet neither of the items provided a solution. Now here's the weird bit - every time I tried checking the system out, I'd get 120 volts showing from the wiring and from the track when I'd test with the multimeter. But the second I'd put a light into the track, the multimeter would drop to zero on the voltage reading on either the wiring or the track. Take the light fixture back out, and the voltage would pop back up. Inserting the light was thus completing some kind of odd loop. It wasn't just one light - I double checked by grabbing working lights from the kitchen track and inserting them into the other track - the same problem would pop up. Finally, having come to the conclusion that there was nothing wrong with the track at all, I took the whole assembly over to a nearby wall outlet, used some spare electric cable to connect up to the appropriate slots - presto, the light came on! I even double checked all this by grabbing another light fixture destined for our bathroom, and tried connecting it to the wiring over the bar. Nothing. Yet as with the track light, the minute I took it over to the wall outlet and connected it, the light worked. So everything logically points to the fact it has to be something to do with this individual circuit, right, because a) the light fixtures work when plugged into another circuit and b) the other three dimmers and lights hooked up in the same box work fine and draw power from the same wire cable/breaker combination. The only things left that I can think of is that the electrician has either wired the dimmer switch up incorrectly or that there's some kind of flaw inside the switch itself. Does this make sense? A friend also told me to double-check to make sure that the black wire feeding power to the light was indeed the hot wire, and it is. If I touch it with the black test lead from the multimeter and put the red one to the neutral I show 120 volts. If I keep the black test lead on the black wire and put the red test lead to the ground - I also show 120 volts. A final point. I know I'm not overloading the circuit - not even close. With all four dimmers maxed and every light on - including the test light on the track - I'd only be drawing 8 amps on a 15 amp breaker, besides which I'm only using one set of lights while I'm working on this problem anyway. This is a dedicated circuit, so there's no additional power being drawn away by something else. So how am I getting 120 volts from this wiring, according to my multimeter, yet it won't light up ANYTHING and keeps giving off the indication that some kind of loop or short is being created every time I actually plug a light into the track? It's got me totally stumped. Anyone have any ideas?
I bought a replacement motor (Dayton 6k778k) for my attic fan. I removed the old one and it has two wires coming out that connect to two wires that go down to the light switch that turns it on. They were connected by those plastic twist things. So, I open up my new motor assuming that there would be two wires coming out of it that I would just connect to the existing wires, however there are just a bunch of blade connectors and I have no idea what is supposed to connect to what and how. I'm attaching three pictures. One is the old motor/wires, the second is the inside of the new motor, and the third is really the only thing that alludes to how this should he hitched up. 3 & 2 were pre-connected out of the box...which leaves 4 & 1. Is one of the wires from the light switch supposed to connect to 4 and one to 1? If so, which one goes to which? Do I need to put blade connectors on the end of the wires that go down to the light switch in order to connect them? Any help is much appreciated.
Am doing a bathroom reno and installed a new fan. Original switch was a simple on off single pole. I want to install a DewPoint condensation fan switch that will turn on automatically at a certain moisture level.
The new switch as 4 wires. green ground, red fan, black power, and white neutral. I know the ground, but how do I hook up the neutral and fan to the existing fan set up? There is a double pole light switch in the same box that has a couple wires to it, and there is a mass of whites that I am not sure where they go Can I hook up the neutral somewhere else, or put it with the fan like a single pole? What do I do with this? In the attached picture the switch on the right is the 2 pole light switch and on the left is the fan switch that I hope to replace. Your Advice is appreciated
i have 3 switch sets in my house that are giving me absolute fits.
#1 kitchen switch, controls the light over the outside door Code: 3 sets of lines coming in, i cannot get this 3 line to work without tripping the breaker every time i turn the switch off #2 bathroom switches Code: power feed line same issue as the first set, flip the switch and trip the breaker (different breaker from the kitchen switch) #3 living room switch and plug controlled via switch Code: power feed line flip switch, trip breaker the switches i have are "1 pole" am i using the wrong switches for this job?
I am only using a simple "non-contact" voltage detector. I am getting a reading from the switch, along part of the line and then at the lights themselves, but the lights are not coming on. I have not gotten into the attic yet to check the line and junction box. What could cause this? An open connection or loose connection? Any help with troubleshooting would be great.
This is a new install of lights, they were not existing. Power is at the switch. Had single pole now I have a double switch. (the existing light that was on the single pole is still working fine). At one point I connected just the new lights to the existing power, single pole switch, and still did not have lights. |