Air Cond Unit Disconnect Switch?

Installing a 4-ton condensing unit outside (240V, 1 ph, MCA= 26A, MOP= 45A).  There will be a HVACR rated 45A breaker at the panel.  Plan to install the 60A non-fused disconnect with GFCI recepticle (GE U065NA1010) next to condensing unit.  Plan to use #8 wire since distance from panel is 80 feet, but unsure of the number of wires.  How many conductors will be required since the disconnect will have a 120V GFCI recepticle.  Will I need 2 wires (2 hots and 1 ground) or 3 wires (2 hots, 1 neutral, 1 ground)?  I'm thinking #8 wire with 3 conductors (2 hots, 1 neutral, 1 ground).
      


Similar Tutorials

How to Lay Sod - The Right Way!
   - Make sure the green side faces up! And, there are a few more steps if you want to ensure a nice looking lawn. Prepa ...
The Difference Between Volts, Amps, and Watts
   - This article explains the difference between Volts, Amps, and Watts in an easy-to-understand non-scientific way. T ...
Water is Leaking from the Toilet – What do I do? (How to replace the wax seal for a toilet.)
   - If there is water leaking from the toilet, you need to make sure that you know from where the water is leaking. Che ...


Similar Topics From Forums

I am installing 200 amp residential service.  From the meter socket I am doing a very short run into the crawlspace to a 200 amp fused disconnect switch. From the disconnect switch I am doing a 60 foot run to the 200 amp panel. The run between the disconnect and the panel is all within the crawlspace interior ( heated ). Do I have to use ACWU cable or is there a cheaper alternative? I also need to isolate the bonding so is 4 wire configuration very common ?   This is a Canadian question specific to British Columbia codes.
      
wanted to get feeback on my crude wiring diagram i put together for my small bathroom remodel. does it appear to be sound or am i way off base??



details:



* 20A dedicated circuit

* 12/2 wiring

* outlet's will be GFCI

* double gang box will contain:

* timer unit for exhaust fan

* double switch for heat lamp and lights

* Ground wiring is not shown but each fixture/outlet/switch will be connected to ground wire

* by calculations, the 34cu box is fine for the number of conductors/size of wiring. per box specs could handle 15/12g wires.

* the scanner cut off the bottom part of the picture, the 2 lights on the right are fed from the same switch, neutral's connected together.



F = Exhaust Fan

L = Light

HL = Heat Lamp

T = Timer switch

S = Switch

H = Hot

N = Neutral

Wire Nuts are in the box connecting the pigtails



Thank you for your input.
      
Getting ready to replace my well jet pump with a 240 volt model (currently I use a 120 volt pump. Currently I have a 20 amp, 120 volt circuit that runs from the house to the pump house about 60 feet. I use that circuit for the pump, a light and a receptacle. I want to replace that circuit with a 20 amp MWBC using 12/3 UF cable from the sub panel in my detached barn to the pump house (about 20 feet).



Question: Can I use 1/2" seal-tite to run from the sub panel to a a junction box prior to going underground with the 12/3 UF? The seal-tight run would be about 30". (I have a bunch of seal-tite, connectors and #12 THWN that I bought cheap at a storage unit auction.) The seal-tite would be run in the stud bay and along side the ceiling joist to get from one side of the barn to the other.



Question: Can I use an unfused air conditioning disconnect at the pump house to disconnect the 2 ungrounded conductors of the MWBC.



I can find nothing in the NEC that would bar either of these items, but I am a code novice.
      
4 gang switch box. power into this box. All wire is 12 Guage.



Neutrals and hots are easy to nut together, 5 at most in 1 nut.



But what about the ground wires? There will be 9 total ends that need to be connected, 9 seems like alot under 1 wire nut.....or is it? lol



Can i make up 2 sets of grounds and use a jumper between the 2 wire nuts?



Do they make a wire nut for 6 wires?
      
Hi all, this is my first post, so...my kitchen was just renovated and the electrical outlets are on the walls and I wanted them in plugmold under the cabinet. Why didn't it happen?  Long story, but I'm doing it myself now.  The electrical receptacles are on 2 separate circuits with a gfci receptacle on each and neither circuit has a receptacle outside the kitchen where I can put the gfci's, so I'm putting gfci breakers in the panel instead. I've run into a different problem on each circuit that'd like some advice on.



Circuit 1: this is a 20 amp circuit.  I have to plug this circuit's neutral wire into the gfci breaker, but I couldn't see which neutral wire matched the hot wire (buried in mess of wires) and I don't have a continuity tester so I just pulled one neutral at a time (tedious) until the circuit failed, but it never failed. So I did this again for every neutral...same result. This circuit shares a few boxes with other circuits so I'm wondering if the neutrals on different circuits are tied together somewhere, and if so I'm pretty sure, but not completely, that that's not going to work with the gfci breaker.  So I didn't install that gfci breaker since I'm not confident it would actually gfci (yep i verbified gfci).  What do you think?



Circuit 2:  this is a 20 amp circuit.  This circuit currently has the refrigerator, gas stove and range hood, and then a gfci in front of 3 electrical receptacles, which already sounds bad since I thought the kitchen receptacles required 2 dedicated circuits. I replaced that breaker with no problem, but it tripped after a few minutes and continued to trip every few minutes. I haven't changed anything else on that circuit yet and it's never tripped before, but now it is, so I put the old breaker back for now. The current gfci receptacle is only protecting the 3 outlets since the appliances are ahead of it. I know you wouldn't normally want the appliances gfci protected, so do you think the refrigerator motor may be a problem?  Do I need the appliances on a separate circuit?  What would you suggest I do?



Thanks, and if you're wondering "why all the effort?", it's partly because I'm meddlesome, partly because I'm bored, and partly because the backsplash tile is to be on showcase, not the electrical receptacles.
      
I'm buying a 12 lead Stamford generator, engine driven, and have a question or two about over current protection and ground fault protection.  I will normally have it wired for single phase 120 and 240 in the double delta configuration.  I may occasionally rewire it for 3 phase 240 in the series delta configuration.



For the single phase setup, what I've read so far leads me to believe I should have a main circuit breaker of about 125% continuous ampacity; it's a 10 kw generator.  Is that correct?  What kind of breaker do I need?  Should this main be a GFCI?  Do I bond neutral and ground?  This is a portable unit so I need to package a load center on the generator frame.  Can I wire one 240 receptacle directly to the main and two or three 120 volt GFCI's on it as well?  Or do I need another 240 breaker downstream of the main?  What should I be thinking about for swithching back and forth between single phase and three phase?  Alot of questions, trying to get smart and be safe.  Thanks.
      
My house has 240v outlet from the previous owner for a kiln of some sort. Im putting a tanning bed in its place. The plug on the tanning bed is a L6-30. I checked specs on the tanning bed and it requires a L6-30 recepticle and a 30amp circuit breaker. I went to the local home fixit store and found the correct recepticle and bought a 2-pole Siemens 30a circuit breaker. After shutting off the main breaker and using testing equipment I pulled out the 50a breaker and replaced it with the 30a..no problem. Heres where Im not sure....The L6-30 recepticle that goes in the wall has a X and a Y and a G marking on it. The G is grounding per instructions, w is white or grey, and X,Y,Z are black, red, blue or etc etc.The wires that come out of the house are red, black and a bare aluminum bradied type wire. Looking at the back from the top counterclockwise  I hooked up the red, then black, then the bare nraided to the G (has green screw) Is the black and red correct? And why doesnt it say red, black and gound?  Can anyone shed some light on this? Thanks!!!
      
I have a 4 prong 220v outlet in my garage and would like to convert it to a 3 prong outlet for my welder and compressor.



Do I just put a wire nut on the neutral and tuck it back in the box?  Then install the new 3 prong outlet using the two hots and ground?



Thanks.
      
Hi guys. I'm Dan, and I'm in Knoxville, TN. I know running power to a shed is a very common topic here. I've been doing tons of reading and feel pretty comfortable with the requirements, but I have two questions I haven't been able to find a clear answer to.



First, my situation: I'm having a 10x16 shed built in my backyard, to be used primarily as a woodshop. I need more than a single circuit, so I know I need a subpanel and two grounding rods at least 6' apart, bonded to the subpanel with #6 bare copper wire.



My house has 200 amp service, and the main panel is in the garage at the opposite corner of the house from where the shed will go, so it would be pretty inconvenient to run a feeder from, there. But there's an existing 100 amp subpanel in the basement, presumably installed when the previous owner finished the basement. I'll be running a 60 amp feeder from that subpanel to the shed.



My total run will be something like 75', so I'm running #6 THWN for the two hots and neutral, and #10 THWN for the ground. I plan to bury it in 1.25" schedule 40 PVC, buried 18" deep.



My first question relates to how I need to run the wire when it's not underground. The basement is finished with a drop ceiling, so I plan to run the feeder across the drop ceiling, out of the house, down to the ground (it's a walk-out basement), then underground the 26' to the shed. I assume it still needs to be in conduit for at least the part that runs up the wall of the house. But what about inside, when it runs through the drop ceiling to the panel? Does it need to be in conduit for the whole run? Or would I just staple the four wires to the joists or something?



The other question relates to the trench. I've got a rain gutter downspout that discharges right at where the shed will soon be, so I'm running a 40' length of 4" PVC to pipe that water past the shed. It will be buried just about 6-12", just enough to run under the shed. Can I run the power conduit in the same trench (obviously, deeper)? Presumably I'd dig the 18" trench to the shed, lay the schedule 40, then add a few inches of dirt to bring it up to about 12" deep, and extend the trench past the shed at that depth, then lay the 4" drain pipe and backfill. Or do I need to dig two separate trenches? Is there a rule about how far apart they need to be if so?



If anyone sees any other flaws or concerns with my plan, please do speak up, I want to do this right. Thanks!



Dan
      
I am in the process of installing a submerisble pump into my well, but I have a few questions I'd like answered first.



The pump is a 1HP, 230V pump with 8.2amps and KW 0.75.  It is rated at 12/2 w/ ground. 



1) Is there any reason I shouldn't install a 230v wall mounted switch to turn this on/off if I want to kill the power.  For now a pump start will control it for my irrigation system, this would just be in addition if I ever wanted to shut things down and not have to rely on using the breaker, which I understand shouldn't be used as a switch.



2) What about installing this on a plug, so that I can plug it into a receptacle vs. hardwired.  (*I'll explain my reason later)



3) My understanding is 12gauge wire is rated for 20amp, but it looks like the owners manual calls for a 25amp fuse.  Should I use 20amp or 25amp?



*The reason I ask about the switch and the plug is because I plan on using some wiring that is already in place.  I already have 12/2 w/ground installed in the location of the pump start.  It is currently wired for 110v as it was placed there for a 3/4hp jet pump I planned on installing, but ended up going with a cased well instead, so I figure why not utilize the existing wire, but switch it to 220 instead of 110.  Basically, swap the 20amp 110v switch out for a similar rated 230v switch and replace the receptacle with a 230v receptacle and just plug this pump in. 



I question the use of the plug because I thought I had read somewhere it was ok to use one, but when unpacking the pump last night, I thought I read never to install it on a plug, so now I'm unsure.  Why would they not want it on a plug?  I guess it's not a big deal as I can always run wire into the j-box, but I hate using pigtails if I don't have to.



Thanks for any info on this...heading to the parts store in a while to grab the fuse and anything else I need.