Wiring A Shed Light & Internal Power

I raised a shed and disconnected the wiring from the main building to the shed. Now it's a month later and it's time to hook the power back up. From the main building I have power into the shed with a white, black, red and copper wire. Originally the power went into the outside light fixture and then off of that it went to another light and two outlets. The original confiruation allowed of us to turn the shed's outside light on and off, from a switch inside the main building. With the power off to the light, we still had power to the outlets and internal light. The outside light fixture has black and white wires. The wire to the internal light and the outlets has a black, white, and copper wire. So how do I wire this so that the main building switch can control the outside light on the shed, while still having power to the internal light and outlets, regardless of the switch being on or off? (I wired the internal blacks and whites all together, which just ended up with the outside light always being on.)
      


Similar Tutorials

How to Lay Sod - The Right Way!
   - Make sure the green side faces up! And, there are a few more steps if you want to ensure a nice looking lawn. Prepa ...
The Difference Between Volts, Amps, and Watts
   - This article explains the difference between Volts, Amps, and Watts in an easy-to-understand non-scientific way. T ...
Water is Leaking from the Toilet – What do I do? (How to replace the wax seal for a toilet.)
   - If there is water leaking from the toilet, you need to make sure that you know from where the water is leaking. Che ...


Similar Topics From Forums

First off, I have read a majority of the posts concerning this subject and they have been very helpful and answered many questions, but I still have a few.



I am wanting to run power to a detached shed that is around 100 feet from the house. However, due to the location of my main panel and the easiest route to run the power, I am looking at running cable about 270 feet. I measured it out to exactly 263 feet, but figured it would be best to go longer. I am wanting to run at least 60 amps to the shed, as I won't be using it for nothing more then power outlets (basic power tools) and lights. Here are my questions:



1) What cable would be best for such a long distance run?



2) Would a 60 amp subpanel be sufficient for this job. I am looking at only 4 circuits: 1 for internal outlets, 1 for lighting, 1 for motion sensor light outside and 1 for external outlet. I am looking at the following panel:

http://www.homedepot.com/Electrical-...&storeId=10051



I have seen some marked 70 amp and wondering if they make a difference:

http://www.homedepot.com/Electrical-...&storeId=10051



3) Also, I will be installing a 30 amp RV connector circuit from my main panel  to the where I park my Camper Trailer, which is a run of about 75 feet. What would be the best cable for this sort of run under ground? Can I run both cable together in the same conduit until I junction if off to where I will be installing the plug for the camper?



4) Would the following be the circuit breakers to use:



60 amp - http://www.homedepot.com/h_d1/N-5yc1...&storeId=10051



30 amp - http://www.homedepot.com/h_d1/N-5yc1...&storeId=10051



I think that is it for now. Thanks in advance for all your help!!
      
I have an outdoor light fixture that I am trying to replace.  The house was built ten years ago.



When I removed the original lamp, I noticed one of the two leads was wired to the ground, and one was wired to the black wire, which is hot per my current sensor.  There are three wires in the box - black, ground (bare copper), and white or neutral, all from a single romex cable.  Unfortunately, I do not recall where the white was when I removed the original. 



I wired the new lamp per the instructions, something I have done many times before - black to black, white to white, and bare copper ground to ground.  Nothing.  The lamp and bulbs are brand new, and I have tried four separate bulbs.  I checked the black and neutral with my current sensor and with the switch on and the lamp installed this way, both show as hot. With the lamp not installed, the switch on, and the wires disconnected only the black shows as hot.  The switch is single pole, and appears to be wired correctly with a black to each screw on one side and a copper ground on the other.



Assuming the new fixture was bad, I reinstalled the old fixture correctly -  black to black, white to white, and bare copper ground to ground.  Still nothing. No light, and I confirmed the bulb is good by putting it in another lamp.   The only way to get it to light is to connect the neutral in the lamp to the bare copper ground.



I capped the wires, turned the circuit back on, and identified all the outlets, switches and fixtures on the same circuit.  I opened every one of them up (four lights and eight outlets) and found three (one switch and two fixtures in another room) where multiple commons connect.  All were properly connected.  My outlet tester shows all outlets as "correct".  I found no instances of grounds connected to commons or vice-versa.



Any ideas?  Is it proper to wire this thing the way I found it?



Thanks for any and all advice!
      
I built a shed and wired it.

I used #8 direct burial from the house to the shed.

I have a breaker in the house 15 amp for just my compressor.

When i run the compressor i seems to drain power from everything else,

ex: all light in the hose fad, my filter on the fish tank stops.

Could some one help me figure this out and put a stop to it.



Thanks Dak
      
I know this has been done to death but, just want to make sure that I headed in the right direction. O.K. I'm building a 12x16 shed and need to know what size wire to use. I plan on having lights, saws, mini fridge, deep freeze, air compressor and maybe a small a/c unit in the summer. I plan on having everything on different circuits like lights on 15A, fridge and freezer on 20A, have plugs on bench on 20A, air compressor on 20A, and mini a/c on 20A. I plan on using romex 14/2 for 15A and 12/2 for 20A. With sub panel http://www.homedepot.com/Electrical-...&storeId=10051 or something like it. My shed is about 30' from the meter loop. So, what size wire do I use from the meter loop 6/2????? Do I need to use a ground rod at the shed? Thanks for looken!!!!!
      
Older house with the metal enclosed wiring has stumped me.  I am attempting to add a second switch for a fan off existing light switch in bathroom.  Existing wiring:  W,B,R from panel, W,B to light.  2 white wire are tied together, two black wires to one contact and red to other contact on switch.  Disconnected all wires and confirmed the black is live from panel.  It seems to me the light is seeing power the entire time since the blacks are connected? I'm confused, please help. how do I add another switch onto this circuit?  Thanks!
      
Hi, I recently moved into a 1954 house with a  20amp electrical system, not the old fuse type, but there are no ground wires.



I removed an old light and replaced it with a light fan combo. As I removed the old light (after turning off the breaker) I noticed from the ceiling that there were 2 white wires tied together with a wire nut and 2 black wires, one attached to the white wire in the light and the other attached to the black one from the light. Feeling this was wrong and should be black to black, white to white, (even knowing full well the light was working fine before I disconnected it) I wired the fan the way I've always wired fan lights,  white to white, blue and black to black.  (again, knowing full well the light was working the other way). Turned breaker on then powered on switch. POP at the switch, breaker switched off. I reworked it back to the way it was before with whites tied off, black to white, black and blue to black, turned it back on and  viola, things worked fine. (I know, duh... Right???)

2 questions from this experience...

1. Why would the 2 whites be tied off with only black wires used?

And 2. It seems that one of the light switches in the same circuit as the blown one is now working soft. In other words, it used to make the normal click noise when turned on/off but now it just moves softly up and down without the click. Could I have damaged something when I mis-wired?
      
Hi,



I would like to wire a switch to be able to cut the power to the ceiling mounted outlets that feed our garage door openers. Running new wiring to them will be a bit cumbersome, so I am hoping to avoid that. The ceiling outlets are powered by light fixtures in the garage (one near by each outlet). There is a 3 wire romex cable running from the light switch to the first light and another one between the lights, and then regular 2 wire romex cables from the light fixtures to the outlets. The red wires in the 3 wire cables to the lights are switchable, the black wires are always hot.



I mainly want to be able to cut the power to the doors when we are away on vacation, and the reason for that is that one night both doors somehow opened up - I have no idea why. I'd hate for that to happen when we're away. Unplugging and plugging in the openers is a bit of a hassle due to the high ceiling.



I thought about wiring in a switched outlet so that I could just reach up with a long handle of some sort and switch off the power to the outlet. It would not be ideal, but definitely easier than getting the ladder out and unplugging the door openers.  However, there is possibly another option that I'd like some input on if anyone cares to comment. I believe I could wire in a switch on the wall next to the light switch that would allow me to cut the power to the black wires in the 3 wire cables. This would cut the power to the ceiling outlets and anything downstream from there (possibly an outside light, I would need to check on that).



My question is, are there any potential issues with this sort of wiring? Is there perhaps any code violation if both hot wires in a 3 wire cable can be switched off separately?



Thoughts?
      
Hi guys. I'm Dan, and I'm in Knoxville, TN. I know running power to a shed is a very common topic here. I've been doing tons of reading and feel pretty comfortable with the requirements, but I have two questions I haven't been able to find a clear answer to.



First, my situation: I'm having a 10x16 shed built in my backyard, to be used primarily as a woodshop. I need more than a single circuit, so I know I need a subpanel and two grounding rods at least 6' apart, bonded to the subpanel with #6 bare copper wire.



My house has 200 amp service, and the main panel is in the garage at the opposite corner of the house from where the shed will go, so it would be pretty inconvenient to run a feeder from, there. But there's an existing 100 amp subpanel in the basement, presumably installed when the previous owner finished the basement. I'll be running a 60 amp feeder from that subpanel to the shed.



My total run will be something like 75', so I'm running #6 THWN for the two hots and neutral, and #10 THWN for the ground. I plan to bury it in 1.25" schedule 40 PVC, buried 18" deep.



My first question relates to how I need to run the wire when it's not underground. The basement is finished with a drop ceiling, so I plan to run the feeder across the drop ceiling, out of the house, down to the ground (it's a walk-out basement), then underground the 26' to the shed. I assume it still needs to be in conduit for at least the part that runs up the wall of the house. But what about inside, when it runs through the drop ceiling to the panel? Does it need to be in conduit for the whole run? Or would I just staple the four wires to the joists or something?



The other question relates to the trench. I've got a rain gutter downspout that discharges right at where the shed will soon be, so I'm running a 40' length of 4" PVC to pipe that water past the shed. It will be buried just about 6-12", just enough to run under the shed. Can I run the power conduit in the same trench (obviously, deeper)? Presumably I'd dig the 18" trench to the shed, lay the schedule 40, then add a few inches of dirt to bring it up to about 12" deep, and extend the trench past the shed at that depth, then lay the 4" drain pipe and backfill. Or do I need to dig two separate trenches? Is there a rule about how far apart they need to be if so?



If anyone sees any other flaws or concerns with my plan, please do speak up, I want to do this right. Thanks!



Dan
      
Hello,



I am replacing a bath light and I am a bit confused by the wiring. I can reattach the wires with the new fixture exactly like the old fixuture was attached but the old fixture did not have a ground connection.



Here is how the wires a



Two whites connected to each other but not to the fixture.

One white and one bare copper wire (I thought it was the ground) connected together and to the white wire of the ligh fixture

one black wire connected to the black wire of the light fixture



How to I connect the the fixture green wire in this configuration?



Thanks
      
We had a pipe disconnect above the downstairs bathroom and the ceiling just about came down, so I decided since it was a hedious looking space, that it was a sign from the gods: Reno time!



Im now at the wiring stage. Originally there was a junction box with a light fixture out one side and a single pole switch(no ground screw...grnd wire attached to the box)on  the other. Typical set up: white from switch marked "hot" or "black" at both ends, and spliced with the incoming power's black wire. Then remaining blacks are spliced together as are the remaining whites... grounded accordingly.



What Im trying to do now is add a GFCI receptical to the mix. But Im having some trouble figuring it all out. NOTE: light fixture is not installed yet, just the wire for it with the ends capped off with a wire nut on each of the wires (Wht/Black/Grnd)



First, whats in the walls: Circuits on a 15 AMP fuse with older (but not the oldest) 12/2 wire with a blue weaved fiber outside cover. Still looks to be in great shape. I've continued using newer, yellow (Lomex or Romex?) 12/2 from homedepot as I've read that you should not mix 14 and 12 together.

All that is on the cicuit is 3 pot lights with 65w bulbs, single bulb on the stairway and what ever goes in the bathroom, so from my math, there should be plenty of room left on the circuit.



What I've tried so far:

A: I spliced the "hot"/"black" white wire from the switch to the incoming power's black, like before. Then I spliced all remaining blacks together with a wire nut, then the same with all remaining whites and then all grounds (did not attach any grnd wire to the Junction box).



Result, Nothing. After switching on the power, I tested the GFCI with a voltage tester as well as the switch and got no read.



B: Undid everything, re-spliced all like to like: all blck together, all white together..etc.



Result: Fuse trips.



Im no electrician, which I imagine is blatantly obvious from the above post, but I am following a Homedepot wiring manual, its just that what Im trying to do is not really addressed in the book... at least not directly. So I've been trying to figure it out by reading every single page, but Im still at a loss.



I've attached a very basic diagram of what is there right now. Any advice would be most appreciated.

Thanks in advance,

John