230v 50amp Wiring For Spa

I need to wire for a spa I'm putting in my back yard. The run from my panel is about 120'. The spa calls for a 230v 50 amp line.



I'm price shopping for the appropriate electrical line but there seems to be a thousand different types of wiring and I need to know what it is I need. A friend told me I probably need 8 guage 4 strand wire.



So if I'm Googling for price what do I call this wiring?

Will 8 guage work for a run that long?
      


Similar Tutorials

How to Lay Sod - The Right Way!
   - Make sure the green side faces up! And, there are a few more steps if you want to ensure a nice looking lawn. Prepa ...
The Difference Between Volts, Amps, and Watts
   - This article explains the difference between Volts, Amps, and Watts in an easy-to-understand non-scientific way. T ...
Water is Leaking from the Toilet – What do I do? (How to replace the wax seal for a toilet.)
   - If there is water leaking from the toilet, you need to make sure that you know from where the water is leaking. Che ...


Similar Topics From Forums

I have a black wire, a brown wire  a blue wire  and a yellow wire with a green stripe coming from the fan. Can I hook this fan up to a 110v line ? If I can , could you tell me which color goes to the blk, the white and the ground. I did try several different ways, the motor did turn, but only at a slow rpm. You have stated that there is a red wire coming from the 230v fan, I do not have a red wire
      
motor #1 came back from servicing and was told it was shot (he said it  was grounded).  i have another motor #2 that im going to see if hell  mount (if it runs).  however motor #2 is designed for 230v.  what needs  to be done to wire this back up considering it is a 120v service.  (i  believe motor #2 was hooked up once before on this service so i know the  power is there)
      
I am in the process of installing a submerisble pump into my well, but I have a few questions I'd like answered first.



The pump is a 1HP, 230V pump with 8.2amps and KW 0.75.  It is rated at 12/2 w/ ground. 



1) Is there any reason I shouldn't install a 230v wall mounted switch to turn this on/off if I want to kill the power.  For now a pump start will control it for my irrigation system, this would just be in addition if I ever wanted to shut things down and not have to rely on using the breaker, which I understand shouldn't be used as a switch.



2) What about installing this on a plug, so that I can plug it into a receptacle vs. hardwired.  (*I'll explain my reason later)



3) My understanding is 12gauge wire is rated for 20amp, but it looks like the owners manual calls for a 25amp fuse.  Should I use 20amp or 25amp?



*The reason I ask about the switch and the plug is because I plan on using some wiring that is already in place.  I already have 12/2 w/ground installed in the location of the pump start.  It is currently wired for 110v as it was placed there for a 3/4hp jet pump I planned on installing, but ended up going with a cased well instead, so I figure why not utilize the existing wire, but switch it to 220 instead of 110.  Basically, swap the 20amp 110v switch out for a similar rated 230v switch and replace the receptacle with a 230v receptacle and just plug this pump in. 



I question the use of the plug because I thought I had read somewhere it was ok to use one, but when unpacking the pump last night, I thought I read never to install it on a plug, so now I'm unsure.  Why would they not want it on a plug?  I guess it's not a big deal as I can always run wire into the j-box, but I hate using pigtails if I don't have to.



Thanks for any info on this...heading to the parts store in a while to grab the fuse and anything else I need.
      
We are in the process of redoing the area around our pool. As part of this we are adding a pool house and hot tub (separate from pool).



I have a couple Elecrtical Contractors coming out this weekend to price/put together a plan. Along with talking to several indivuals, I've been lurking around reading and trying to gather info but feel the need to have as much info available prior to getting these estimates and plans. Please excuse any incorrect verbage i might use and appreciate any corrections to my terminoligy



So this is what i have 



The pool house is approx 100 ft from the house.

It will have a few and outlets for blenders, minifridge, tv etc

the pool equipement consites of a pump, heater and a sand filter. The pump and current heater run off standard 110 lines (however if i upgrade this I dont know if the new one will require a 220 line



The pool light seems to run off a standard line as well



The hottub requires a 220 40amp line



There will be landscaping lighting as well as 2 more outlets for accesories



The original setup prior to last year had what looks like 6 or 8 guage (3 wire) directly buried about 6-8 inches under  ground. it was running what look to be two 20amp circuits from the main panel inside the house. This wire got split to two separate outlets near the pool. One went directly to the pool equipment and on directy to the pool light switch and some landscaping ighting.



With all the enhancements we are making i'm wondering what the best approach will be.



I assume a sub panel in the pool house that has one "main breaker" and has its own ground. Then one run to the pool equipment and one run to the hottub and a couple runs to the accesories i mentioned.



I have seen several replies on here where individuals talk about  "if they were doing the job this is how they would do it". Id be interested in some responses



What type of wire would be best to get it to the pool house

Does it run right from the main panel in the house?

Does direct burial make sense or shold i put it in conduit? I'm already digging a trench three feet deep for water and RG6 (which will be pushed thru conduit)



Any question i should make sure i ask the contractors?





Thanks in advance for any input
      
I want to run a Cat 5 line from my phone box outside to a jack inside to connect my phone and DSL. Right now I just have a regular phone line for both and the phone company recommends running a new line because the internet is always slow and I can't call out on my phone.



How do I know which wires to hook up outside?



Kevin
      
I am replacing a feed through breaker panel the bus bar and breaker was inverted but the main breaker is up and down with on being down and I also noticed that the plastic in the back that holds the bus bar is cracked.



I bought a newer model from the same manufacture that has a much better design and a better main breaker.  But unlike the one I already have when you invert it the breaker slots don't line up and cover does not fit properly.



I was thinking about just cutting out the center where the breaker slots are.  I measured and if I cut it just right all I have to do is turn it over and it will line up just have to bolt or weld it in place.  Would this be legal



I also thought about putting the panel the way it came and feeding the bus bar hot and keeping the panel under the 6 throw rule.  Or would that not work because I am using feed through.  There will be 4 double pole breakers and the one main that feeds a sub panel.





I really hate the cheap design of this panel.







I plan to replace it with this.




      
First off im in So Cal. and a few months back my pool equipment stoped working after a rain storm. I have an underground conection that is accseible through a plastic box in the concrete. There is a water proof box there that housed the wiring as it runs from 220 breaker underground to the pool equip., I opened it to find it full of water. The short burned the wiring some where under some 60 feet of cement. I forgot to mention the wiring in existing conduit will not pull through have tried several times even as despreate as a come-along.



Ive had an electrician and Genral contractor both look at it and both said wiring is fried, but im looking for advice on my two options.



1st is cutting a trench in the cement about 60 to 70 feet from circuit breaker to pool equipment. Then using conduit the whole lenght like it was previously but no under ground box. Just two connections breacker & pool Equip.



2nd option the breaker is near my atic. run power from breaker through the house atic to where pops out on the other side of the house. would be about 50 feet through atic and about another 50 feet of conduit 25 above ground attached to eves and 25 below ground to pool equipment. This is a similar route as the gas line to pool equipment they will come out of atic about 20 feet apart then eventually follow similar path is this a problem?? I was told to use 12-3 Romex?? Suggestions on which route to take would be great. Atic is clearly easyer but concerend with closeness to gas line. Thanks before hand for the help
      
In a previous thread (Wire suitable for underwater usage), I enquired about what cord types would be suitable for underwater usage because I was building a submersible fishing light to attract baitfish.  Well, the light is done, and the bulb "farthest away" from the battery is by far the brightest in the chain (I hesitate to say chain since they are wired in parallel). 



Attached image "photo 1" is a picture of the light I made.  Notice the bulb all the way to the left is far brighter than the rest.



All bulbs used are the same spec, and look like this:



To wire the bulbs, I cut the flange off with a Dremel tool so that they would fit in the tube.  Two pair of them have their terminals soldered together (neg to neg, pos to pos...that's the "gap" you see in the lighting), and the first bulb in line is upside down, with it's terminals facing the incoming wiring.  The first bulb receives the wiring from the main line, then hookup wire is used to jump from those terminals to the next set, etc. 



There IS one anomaly with the final/far left bulb.  When I was cutting off the flange, I accidentally cut too far on that piece, basically severing the terminals from the bulb.  So, when wiring it into the circuit, I had to improvise and soldered the hookup wire directly into the solder points located on the bulb itself (instead of the underside).  Hopefully you can see what I'm talking about in attached "photo 2."



I have no idea why this anomaly would make the bulb brighter though.  Can anyone think of any other reason the bulb would be brighter?  Unfortunately, I cannot do any readings on the individual bulbs because I did not notice this until everything was soldered into place and the lamp sealed/waterproofed).
      
I am thinking of purchasing a WineKoolr used but after looking at the manual online it states that it must be plugged into a "Dedicated separately fused, grounded, 15 amp 100-120v line." The price I can get this at is awesome, but I live in apartment and am not sure, but think I only have 1 dedicated line at all, for the fridge. The previous owners said they just had it plugged into a normal outlet fine, but I want to know if it is a serious issue to do this? I really want a nice cooler for my beer cellar since I have no actual basement, so I am really hoping I can make this work in my home. Thanks for any help!





*Someone asked me on another forum what breakers I have for where I want to install it, and its in my second bedroom.  The breaker for those outlets is a 15A.  They also said that it probably says that in the manual to cover themselves legally but I should likely be just fine.





**

Well I turned off the breakers until I found which was for the outlets in the spare room.  As far as I can tell, the only things on this circuit are the spare bedroom outlets (not the lights), and 1 outlet in the hallway.  Nothing is plugged into any of these and its a 20A circuit.
      
I recently switched over from AT&T phone/cable/Internet service to Cablevision. 



The problem with both services is the coax cable coming through a hole in the wall from outside and then a phone line from their modem stapled to the floor board and tied into the phone outlet inside.  Then there's my phone lines, the coax cable to the TV... It's a disgusting mess.



I'd like to install a combination phone line and cable outlet in the wall and get rid of as much loose wiring as possible.  The phone line would come through the same area as the cable and I'd wire it on the other end to the main box outside the house.



I have no experience with this so my question is can I take the phone line from the Cablevision modem and simply plug it into the outlet and get all the phones in the house to work or does it have to be hard wired or piggybacked inside the outlet?